Hoshizaki F-1530/2030 MK2 Flakers Ice Machine Codes
| Code | Meaning | What to check |
|---|---|---|
| 1 beep | Low-water safety: the upper float switch stayed open more than 90 seconds after the inlet valve energized. | Resets on its own once the water supply is restored and the float switch closes. How to fix → |
| 2 beeps | Control switch left in DRAIN for more than 15 minutes. | Resets on its own when the control switch is moved back to ICE. |
| 3 beeps | High-pressure switch: first or second trip within 1 hour. | Resets on its own once pressure drops and the switch closes. How to fix → |
| 4 beeps | High-pressure switch: third trip within 1 hour. | Call for service. Hoshizaki recommends leaving the icemaker off until this alarm is resolved to avoid a possible catastrophic failure. Manual reset (power off and on). How to fix → |
| 5 beeps | Freeze timer: inlet valve off more than 30 minutes since it last energized. | Manual reset (power off and on). How to fix → |
| 6 beeps | Low voltage: 92 VAC ±5% or less. | The POWER LED turns off while voltage protection is active. Resets on its own when the voltage is corrected. |
| 7 beeps | High voltage: 147 VAC ±5% or more. | Resets on its own when the voltage is corrected. |
| 8 beeps | Gear motor: the compressor control relay contacts failed to close. | Manual reset (power off and on). |
| 9 beeps | Bin control fault: BC1 (ultrasonic sensor) failed with S2 dip switch 7 on, and the BC2 mechanical backup paddle engaged. | Manual reset (power off and on). |
How to read the codes
- When a safety trips, the unit shuts down and the board beeps the alarm number every 5 seconds. Count the beeps.
- Alarms 1, 2, 3, 6 and 7 reset on their own once the cause is gone. The rest need a manual reset: turn the power off and on again.
- The POWER LED shows proper control voltage. Sequence LEDs: fill = WTRIN (inlet valve); ice purge = GM (gear motor, 5 minutes); freeze = GM and COMP, with WTRIN on during refill until the upper float switch closes (alarm after 90 seconds); 1-in-1 drain = FLUSH (2 seconds).
- To skip the 5-minute ice purge while diagnosing, press SERVICE on the control board after the gear motor starts (live terminals nearby).
- This list is shorter than the one in Hoshizaki's F-422 to F-1022 MAK manual: it has no evaporator thermistor alarms and no 10-beep alarm. Use the chart for your model.
- Abbreviations: BC1 bin control (ultrasonic sensor), BC2 bin control 2 (mechanical backup), CB control board, CCR compressor control relay, DV drain valve, GM gear motor, LLV liquid line valve, SLV suction line valve, UFS upper float switch, WV inlet water valve.
Alarms point to a circuit, not a part. Test before replacing a board, thermistor or valve, and never bypass a safety to keep the machine running. Line-voltage work is for trained technicians, refrigerant work requires EPA 608 certification, and ice that touched a contaminated machine should be discarded.
Source: Hoshizaki Modular Flaker Service Manual, F-1530M_K(Z)2 and F-2030M_K(Z)2/3, No. 73268 (issued 7-6-2026), LED Lights and Audible Alarm Safeties p. 44. The "meaning" column follows the manufacturer's wording; "what to check" is our field summary. Always go by the label on the unit you're working on.
Related
- Commercial ice machine troubleshooting (no ice, freeze-ups, harvest problems)
- Commercial refrigeration practice test
- Look up any ice machine code
Other brands
- Hoshizaki KM-901M/1100M/1340M/1601M J Series (modular crescent cubers: KM-901M_J, KM-1100M_J, KM-1340M_J, KM-1601MRJ)
- Hoshizaki KM-350/420/520/660M J Series (modular crescent cubers: KM-350MAJ, KM-350MWJ, KM-420MAJ, KM-420MWJ, KM-420MRJZ, KM-520MAJ, KM-520MWJ, KM-520MRJ, KM-520MRJZ, KM-660MAJ, KM-660MWJ, KM-660MRJ, KM-660MRJZ)
- Hoshizaki KM MAK Series (modular crescent cubers: KM-322MAK, KM-330MAK, KM-522MAK, KM-530MAK, KM-622MAK, KM-730MAK, KM-930MAK2, KM-1130MAK2)
- Hoshizaki F MAK Series Flakers (modular flakers and cubelet: F-422MAK, F-622MAK-C, F-622MWK-C, F-622MRKZ-C, F-822MAK, F-822MWK, F-1022MAK, F-1022MWK, F-1022MRKZ, F-1022MLKZ; -C, -SC and -CB cubelet versions)
- Scotsman Prodigy and Prodigy Plus Cubers (modular cubers C0322, C0522, C0722, C0330, C0530, C0630, C0830, C1030, C1448, C1848, C2148)
- Scotsman Prodigy Flaker and Nugget (flaked F0522, F0822, F1222, F1522; nugget N0422, N0622, N0922, N1322; includes Prodigy Plus D series)
- Manitowoc Indigo NXT (air, water and remote cubers and flakers: IDT0300, IDT0420, IDT0450, IDT0500, IDT0620, IDT0750, IDT0900, IDT1200, IDT1500, IDT1900, IYT0300, IYT0420, IYT0450, IYT0500, IYT0620, IYT0750, IYT0900, IYT1200, IYT1500, IYT1900, IRT0500, IRT0620, IRT0750, IRT0900, IRT1900, IDF0300, IDF0500, IDF0600, IDF0900, IYF0300, IYF0500, IYF0600, IYF0900, IRF0900)
Did you find your code?
One field tip a week
A short, practical HVAC tip in your inbox every week: diagnostics, charging, airflow and code changes. Free, unsubscribe anytime.
We'll only use your email for the newsletter. Privacy policy.
HVAC Cheat Sheet · Free PT charts, code lookups and calculators for techs at hvaccheatsheet.com