Home / Charts / Hoshizaki ice machine codes

Hoshizaki F-1530/2030 MK2 Flakers Ice Machine Codes

Applies to: Hoshizaki F-1530/2030 MK2 Flakers (modular flakers: F-1530MAK2, F-1530MWK2, F-1530MRKZ2, F-2030MWK2, F-2030MRKZ2, F-2030MRKZ3, F-2030MLKZ; -C and -SC cubelet versions). Beeps every 5 seconds from the control board.

CodeMeaningWhat to check
1 beepLow-water safety: the upper float switch stayed open more than 90 seconds after the inlet valve energized.Resets on its own once the water supply is restored and the float switch closes. How to fix →
2 beepsControl switch left in DRAIN for more than 15 minutes.Resets on its own when the control switch is moved back to ICE.
3 beepsHigh-pressure switch: first or second trip within 1 hour.Resets on its own once pressure drops and the switch closes. How to fix →
4 beepsHigh-pressure switch: third trip within 1 hour.Call for service. Hoshizaki recommends leaving the icemaker off until this alarm is resolved to avoid a possible catastrophic failure. Manual reset (power off and on). How to fix →
5 beepsFreeze timer: inlet valve off more than 30 minutes since it last energized.Manual reset (power off and on). How to fix →
6 beepsLow voltage: 92 VAC ±5% or less.The POWER LED turns off while voltage protection is active. Resets on its own when the voltage is corrected.
7 beepsHigh voltage: 147 VAC ±5% or more.Resets on its own when the voltage is corrected.
8 beepsGear motor: the compressor control relay contacts failed to close.Manual reset (power off and on).
9 beepsBin control fault: BC1 (ultrasonic sensor) failed with S2 dip switch 7 on, and the BC2 mechanical backup paddle engaged.Manual reset (power off and on).

How to read the codes

Alarms point to a circuit, not a part. Test before replacing a board, thermistor or valve, and never bypass a safety to keep the machine running. Line-voltage work is for trained technicians, refrigerant work requires EPA 608 certification, and ice that touched a contaminated machine should be discarded.

Source: Hoshizaki Modular Flaker Service Manual, F-1530M_K(Z)2 and F-2030M_K(Z)2/3, No. 73268 (issued 7-6-2026), LED Lights and Audible Alarm Safeties p. 44. The "meaning" column follows the manufacturer's wording; "what to check" is our field summary. Always go by the label on the unit you're working on.