Head Pressure Control on Refrigeration Systems: Valves, Fan Cycling, Settings and Winter Charge
An air-cooled condenser sized for a summer afternoon has far too much capacity on a winter night. Head pressure falls with the outdoor temperature, and a refrigeration system can't simply shut down for the season the way a comfort cooling system does: the box still needs cooling. Sporlan's Bulletin 90-30 lists what goes wrong without head pressure control:
- Starved evaporator. The pressure difference across the expansion valve port sets how much it can feed, so low head pressure means too little refrigerant reaches the evaporator.
- Hot gas functions stop working. Hot gas defrost and hot gas bypass need normal head pressure. Without it you get low suction pressure and iced coils.
- Off-cycle migration. Refrigerant migrates to the cold condenser during the off cycle. The evaporator pressure may never build to the low pressure control's cut-in, or the system starts and short cycles on low suction.
The walk-in condensing unit guide has Heatcraft's full cold-weather troubleshooting rows. This guide covers how the controls work, where they're set and how to charge a system that has them.
The four methods
Heatcraft's condensing unit manual lists four kinds of head pressure control on its units: a dual valve system, a single valve system, ambient fan cycle control, and variable speed fan control.
| Method | How it holds head pressure | Notes |
|---|---|---|
| Single flooding valve (Sporlan LAC, OROA) | Backs liquid up in the condenser and meters hot gas to the receiver | Usually fixed setting; needs extra winter charge |
| Dual valve (ORI + ORD) | ORI throttles liquid leaving the condenser; ORD bypasses hot gas to the receiver | ORI is adjustable; needs extra winter charge |
| Ambient fan cycling | Thermostats turn condenser fans off as the outdoor temperature drops | Approximate; doesn't respond to load |
| Pressure fan cycling or variable-speed fans | Fans cycle or slow on head pressure | Often added alongside a valve to reach setpoint faster |
How the valves work
LAC (Low Ambient Control). A three-way modulating valve. On the LAC-4, discharge pressure works against the dome pressure: when it falls below the dome setting, the valve opens the discharge port so hot gas bypasses the condenser. Mixing hot gas into the condenser's outlet raises the pressure there, slows the flow out of the condenser and backs liquid up into it. A flooded condenser has less surface to condense on, so condensing pressure rises. In summer, discharge pressure holds the discharge port shut and liquid flows freely from condenser to receiver. The LAC-5 and LAC-10 do the same job but respond to receiver pressure.
OROA. A nonadjustable valve (Open on Rise of Outlet pressure) that controls on receiver pressure: as receiver pressure drops, it throttles liquid leaving the condenser, and an ORD built into it bypasses hot gas to the receiver.
ORI/ORD. The ORI (Open on Rise of Inlet pressure) sits in the liquid drain line between the condenser and receiver and responds to condensing pressure only. As the outdoor temperature drops and condensing pressure falls toward its setting, it throttles. The ORD (Opens on Rise of Differential) sits in a hot gas line around the condenser. When the ORI throttles, the pressure difference across the ORD rises; at its setting the ORD opens and sends hot gas to the receiver, reaching full stroke at 10 psi above its setting. The hot gas warms the cold liquid so it reaches the receiver with enough pressure to feed the expansion valve.
Check valve. Sporlan calls for an auxiliary check valve in the line between the LAC and the receiver, so refrigerant can't migrate from the warm receiver to the cold condenser during the off cycle.
Settings
Heatcraft walk-in condensing units (current manual):
| Control | Medium temperature | Low temperature |
|---|---|---|
| Single valve (standard, nonadjustable) | About 145 psig | About 100 or 145 psig, depending on the model |
| Dual valve: adjust the ORI to | 150 psig | 100 psig |
| Variable speed fan control | 145 psig | 100 or 145 psig, depending on the model |
Heatcraft notes that the 100 psig valve is sometimes used on medium temperature systems for efficiency, and that adjustable single valves come preset to the same pressures as the nonadjustable ones. These lower settings are tied to the DOE walk-in efficiency (AWEF) rules; Heatcraft's AWEF installation guidelines note that typical minimum settings were 170 to 180 psi before those rules took effect, so an older unit may be set higher. See DOE set points.
Adjusting an ORI (Heatcraft dual valve units): gauges on the compressor discharge port; turn the stem clockwise to raise discharge pressure, counterclockwise to lower it. Adjust in mild or cold weather. In warm weather you may not be able to get it as low as you want, and it may need readjusting once it turns cold.
Sporlan's general rule (Bulletin 90-30, 2012): set the control at the equivalent of about 90 to 100°F condensing, or 80 to 90°F in the receiver, which means the valve starts throttling at outdoor temperatures below about 70°F. Sporlan says a higher setting usually isn't necessary or economical. Its standard fixed settings at the time were 100 psig for R-134a, 180 psig for R-22, R-407C and R-502, and 210 psig for R-402A, R-404A and R-507. The ORI adjusts over a nominal 65 to 225 psig, and the standard ORD opens at 20 psi.
Read the valve before you replace it. The setting is stamped on the valve body. Sporlan notes that many valves in the field have special settings and should be replaced with the same valve. A dual-setting LAC-4-DS (for example 100/180) holds the higher setting with its capillary intact; clipping and re-fusing the capillary drops it to the lower setting. Fuse the tip right after clipping so moisture can't get into the element.
ORD and pressure drop. The standard 20 psi ORD suits systems where the drop through the condenser, the ORI or OROA and the piping is under 14 psi. Higher drops, from a long condenser circuit or heat reclaim coils piped in series, can hold the ORD in bypass all the time; Sporlan makes higher-setting ORDs for those. To check, compare compressor discharge pressure with receiver pressure at full load with a normal condensing temperature.
Fan cycling
Ambient fan cycle thermostats. Heatcraft's Table 1 gives approximate thermostat settings by the unit's design TD. The settings don't account for load.
| Design TD (°F) | T1, all units (°F) | T2, 3-, 6- and 8-fan units (°F) | T3, 8-fan units (°F) |
|---|---|---|---|
| 30 | 40 | 30 | 20 |
| 25 | 45 | 35 | 25 |
| 20 | 50 | 40 | 30 |
| 15 | 55 | 45 | 35 |
2- and 4-fan units use T1 only. Cycle pairs of fans on double-wide units.
Pressure fan cycling. Heatcraft's recommended settings, used on the fan nearest the compressor with ambient fan cycling on the others:
| Head pressure valve setpoint | Cut-in | Cut-out |
|---|---|---|
| 150 psi | 175 psi | 140 psi |
| 100 psi | 125 psi | 90 psi |
The manual's text refers to this as Table 15; the table itself is labeled Table 18.
Never let every fan cycle off one control. Heatcraft requires at least one condenser fan to run whenever the compressor runs, positioned to blow over the compressor body. On units with several condenser motors, all of them may never cycle off one control. The same principle applies to the AC side: see condenser fan not running for the cases where a comfort cooling unit stops its fan on purpose.
Winter charge: why the charge matters most
A flooding valve can only hold head pressure if the system has enough refrigerant to fill part of the condenser. Sporlan says the valve setting makes no difference if the system is short of refrigerant, and Heatcraft says dual valve units need enough charge to partially flood the condenser in low ambient conditions.
Heatcraft's charge tables are built on these assumptions:
- Winter charge: a 90% flooded condenser coil.
- Summer charge: 10% flooded (25% on units with a subcooling circuit).
- Receiver: 15 to 20% of its volume for the liquid seal.
The difference between the two is the extra charge listed for each model. On Heatcraft's small R-404A units it runs from about 1 lb on a small microchannel unit to 6 lb on a large round-tube unit, with correction factors for other refrigerants. Heatcraft calls these approximate and says to add the liquid line and unit cooler for total charge. Use the table for your model; don't add more than prescribed.
Charging by a clear sight glass on a head pressure system (Heatcraft): the condensing temperature must be above 105°F while you charge. If it isn't, cut the condenser's face area (or the air going through it with fans still running) to raise discharge pressure above the equivalent of 105°F, charge until the sight glass clears, adjust evaporator superheat, then restore the full face area and let the system balance. Charging to a clear glass in cold weather without doing this leaves the system short for winter.
Bad valve or short charge?
| What you see | Most likely | Check |
|---|---|---|
| Head pressure low in cold weather, bubbles in the sight glass, receiver level low | Short charge (not enough to flood the condenser) | Leak check, repair, then charge to the manufacturer's winter charge |
| Head pressure below the stamped setting with a full charge | Valve not bypassing, or head pressure building too slowly | Add pressure fan cycling (Heatcraft); then replace the valve |
| Condenser always bypassing, head pressure high in mild weather | ORD or OROA held in bypass: Sporlan notes a drop above 14 psi between compressor and receiver can do this | Measure discharge vs receiver pressure at full load; use a higher-setting ORD if the drop is high |
| Won't start after a cold night, short cycles on low pressure | Refrigerant migrated to the condenser | Check valve between the valve and receiver; low ambient kit; low pressure switch setting |
| Slow pull-down in cold weather | Expansion valve too small at minimum head pressure | Temporarily reduce condenser face area during pull-down; resize the valve (Heatcraft) |
Heatcraft's own cold-weather rows (short cycling on the low pressure switch, head pressure that never reaches its minimum, low compressor superheat, slow pull-down) are laid out with their fixes in the walk-in condensing unit guide.
FAQ
What is head pressure control in refrigeration?
A way of keeping condensing pressure high enough in cold weather for the expansion valve to feed the evaporator. Valves flood the condenser with liquid and send hot gas to the receiver; fan cycling and variable-speed fans cut condenser airflow.
What should head pressure control be set at?
Follow the unit's manual. Heatcraft's current walk-in condensing units use about 145 psig on medium temperature and 100 or 145 psig on low temperature. Sporlan's older general rule was the equivalent of about 90 to 100°F condensing.
How does a head pressure control valve work?
On a single flooding valve like Sporlan's LAC, when discharge pressure falls below the dome setting the valve lets hot gas bypass the condenser. That raises the pressure at the condenser outlet, backs liquid up into the condenser and cuts its working surface, so condensing pressure rises back to the setting.
Why won't my head pressure come up in cold weather?
Usually a short charge: the flooding valve needs extra refrigerant to fill the condenser in winter, and Sporlan says the setting makes no difference if the system is short. After that, look at a valve that isn't bypassing, or add pressure fan cycling so head pressure reaches the setpoint faster.
Can I cycle all the condenser fans off in winter?
No. Heatcraft requires at least one condenser fan to run whenever the compressor runs, positioned over the compressor body, and never all fans cycling off one control.
Sources
- Sporlan Bulletin 90-30, Head Pressure Control Valves for High and Low Ambient Stability (July 2012), distributor-hosted copy: operation pp. 2-4, application and settings pp. 4-5
- Heatcraft DOE AWEF system installation and adjustment guidelines
- Heatcraft Condensing Units Installation and Operations Manual H-IM-CU: head pressure control and Table 1 p. 6, charging p. 24, flooding charge tables p. 25, Table 17 and Table 18 p. 35
Was this guide useful?
One field tip a week
A short, practical HVAC tip in your inbox every week: diagnostics, charging, airflow and code changes. Free, unsubscribe anytime.
We'll only use your email for the newsletter. Privacy policy.
Tools for this job
Low Pressure Control Settings
Sporlan's cut-out and cut-in for coolers, meat cases and freezers on R-448A, R-454B, R-22 or R-513A, with the saturation temperature behind each, and how far off your current settings are.
SH/SCSuperheat & Subcooling Calculator
Enter your line temps and saturation temps; get superheat and subcooling instantly.
Related guides
Walk-In Condensing Units: Preventive Maintenance and Cold-Weather Problems
The quarterly, semi-annual and annual maintenance Heatcraft lists for air-cooled walk-in condensing units, what to check when a unit short cycles or won't hold head pressure in cold weather, pressure fan cycling settings, and the extra rules for A2L condensing units.
Hot Gas Defrost: Three-Pipe, Reverse Cycle and Alternating Systems Explained
How hot gas defrost works on walk-in and warehouse unit coolers, the difference between three-pipe, reverse cycle (two-pipe), alternating evaporator and Thermobank systems, the drain pan loop and check valves, the 25% rule, piping and start-up checks, and what to look at when the coil won't clear, following Heatcraft and HTPG unit cooler manuals.
AC Condenser Fan Not Running or Spinning: Capacitor, Motor or Controls?
Why an outdoor AC or heat pump fan won't turn on, spins slowly, or stops along with the compressor. Normal fan-off cases, the fan capacitor, bearings, motor windings, the contactor and control board, from Carrier's service manuals.
Reversing Valve Troubleshooting: Heat Pump Stuck in Heat or Cool
How to tell whether a heat pump that won't switch modes has a bad solenoid coil, a control problem, a stuck slide or an internally leaking reversing valve, using voltage, coil resistance, temperatures and pressures.
Field reference for trained technicians. Always follow the equipment manufacturer's instructions, local code and safe work practices. See our editorial standards, or report a correction.