Low Pressure Control Settings
Pick the application and refrigerant to get Sporlan's approximate low pressure control cut-out and cut-in, with the saturation temperature each one stands for. Enter what the control is set to now and the tool shows how far off it is, in psig and in degrees.
Covers: Beverage cooler.
Saturation temperatures use the dew point column on the same Sporlan card (covers 0 to 120 psig). Sporlan's settings are approximate and assume a suction line pressure loss equal to 2°F. The equipment manufacturer's settings come first; check the control against a gauge you trust. See walk-in troubleshooting.
Sporlan's table
From Sporlan's pressure-temperature card (Form 1-725, © 2025), "Approximate Pressure Control Settings," in psig. Sporlan notes the settings assume a suction line pressure loss equivalent to 2°F.
| Application | Box °F | TD °F | R-22 out / in | R-448A out / in | R-454B out / in | R-513A out / in |
|---|---|---|---|---|---|---|
| Beverage cooler | 35 to 38 | 15 | 41 / 66 | 42 / 69 | 67 / 103 | 21 / 38 |
| Floral, produce and smoked meat coolers, meat reach-thru, service deli, seafood | 32 to 35 | 15 | 38 / 62 | 39 / 64 | 63 / 97 | 19 / 35 |
| Multi-deck fresh meat case | 26 to 29 | 15 | 32 / 54 | 33 / 56 | 54 / 86 | 15 / 30 |
| Frozen glass door case, frozen walk-in | -10 to 0 | 10 | 9 / 24 | 9 / 24 | 21 / 43 | 0 / 10 |
| Frozen ice cream, open-type frozen food case | -30 to -20 | 10 | 0 / 10 | — | 7 / 23 | — |
Reading the numbers
- Cut-out is the suction pressure where the control opens and stops the compressor; cut-in is where it closes and restarts it. The difference is the differential.
- Look at the saturation temperatures: on every row of Sporlan's table, the cut-in works out to about the top of the box temperature range.
- R-448A and R-454B are blends with glide, so the tool uses Sporlan's dew point column, which matches the evaporator outlet.
- These are a starting point. The condensing unit or case manufacturer's settings come first, and Heatcraft says to verify cut-in and cut-out with a gauge of known accuracy at start-up.
Related: walk-in cooler and freezer troubleshooting, walk-in condensing units and cold weather, commercial refrigeration practice test.
Source
Sporlan Division, Parker Hannifin, Pressure-Temperature Chart, Form 1-725 (© 2025): approximate pressure control settings and PT tables, back and front pages. Read from the printed tables.
Was this tool useful?
One field tip a week
A short, practical HVAC tip in your inbox every week: diagnostics, charging, airflow and code changes. Free, unsubscribe anytime.
We'll only use your email for the newsletter. Privacy policy.
Related tools
Superheat & Subcooling Calculator
Enter your line temps and saturation temps; get superheat and subcooling instantly.
TSHTarget Superheat Calculator
Target superheat for piston and cap-tube systems from indoor wet bulb and outdoor dry bulb.
80%Recovery Cylinder Fill Calculator
Water capacity, tare weight and refrigerant in; the most the scale should read and how many pounds of room are left out.
Results are estimates for field reference. Always confirm against the equipment manufacturer's charging chart, installation instructions and local code. Found a problem with this tool? Tell us.