Low Pressure Control Settings

Pick the application and refrigerant to get Sporlan's approximate low pressure control cut-out and cut-in, with the saturation temperature each one stands for. Enter what the control is set to now and the tool shows how far off it is, in psig and in degrees.

psig
psig

Covers: Beverage cooler.

Sporlan cut-out
42psig
Sporlan cut-in
69psig
Differential
27psig
Cut-out saturation
18°F
Cut-in saturation
38°F

Saturation temperatures use the dew point column on the same Sporlan card (covers 0 to 120 psig). Sporlan's settings are approximate and assume a suction line pressure loss equal to 2°F. The equipment manufacturer's settings come first; check the control against a gauge you trust. See walk-in troubleshooting.

Sporlan's table

From Sporlan's pressure-temperature card (Form 1-725, © 2025), "Approximate Pressure Control Settings," in psig. Sporlan notes the settings assume a suction line pressure loss equivalent to 2°F.

ApplicationBox °FTD °FR-22 out / inR-448A out / inR-454B out / inR-513A out / in
Beverage cooler35 to 381541 / 6642 / 6967 / 10321 / 38
Floral, produce and smoked meat coolers, meat reach-thru, service deli, seafood32 to 351538 / 6239 / 6463 / 9719 / 35
Multi-deck fresh meat case26 to 291532 / 5433 / 5654 / 8615 / 30
Frozen glass door case, frozen walk-in-10 to 0109 / 249 / 2421 / 430 / 10
Frozen ice cream, open-type frozen food case-30 to -20100 / 10—7 / 23—

Reading the numbers

  • Cut-out is the suction pressure where the control opens and stops the compressor; cut-in is where it closes and restarts it. The difference is the differential.
  • Look at the saturation temperatures: on every row of Sporlan's table, the cut-in works out to about the top of the box temperature range.
  • R-448A and R-454B are blends with glide, so the tool uses Sporlan's dew point column, which matches the evaporator outlet.
  • These are a starting point. The condensing unit or case manufacturer's settings come first, and Heatcraft says to verify cut-in and cut-out with a gauge of known accuracy at start-up.

Related: walk-in cooler and freezer troubleshooting, walk-in condensing units and cold weather, commercial refrigeration practice test.

Source

Sporlan Division, Parker Hannifin, Pressure-Temperature Chart, Form 1-725 (© 2025): approximate pressure control settings and PT tables, back and front pages. Read from the printed tables.

Related tools

Results are estimates for field reference. Always confirm against the equipment manufacturer's charging chart, installation instructions and local code. Found a problem with this tool? Tell us.