Hot Gas Defrost: Three-Pipe, Reverse Cycle and Alternating Systems Explained
Electric defrost melts frost with heaters bolted to the coil. Hot gas defrost uses the system's own heat: discharge gas from the compressor is routed through the evaporator, warms the coil from the inside and melts the frost. It's common on larger walk-in freezers, warehouses and multi-evaporator systems because it defrosts faster and doesn't need heater circuits sized for every coil.
This guide follows Heatcraft's unit cooler installation manual (H-IM-UC) and HTPG's manual for medium profile, heavy duty and warehouse unit coolers. Heatcraft builds the Bohn, Larkin, Climate Control and Chandler brands; HTPG builds Kramer, Russell and Witt. Controllers, valve arrangements and setpoints vary by system, so use the manual for the equipment on the job.
The pan loop and why it matters
On a hot gas unit cooler, the hot gas goes through a drain pan loop before it reaches the coil. That keeps the condensate in the pan from refreezing while the coil melts. Heatcraft's Chandler low-profile technical guide lists the hot gas loop on the bottom of the coil, for easier access, as standard on its hot gas models. If the coil clears but the pan ices up, the pan loop is the first thing to look at.
Three-pipe (re-evap) systems
Three pipes run to each evaporator: liquid, suction and a hot gas line.
- Hot gas is taken from the discharge line between the compressor and the condenser.
- A hot gas solenoid valve opens to send it through the drain pan loop, then into the distributor tee and through the coil.
- Heatcraft says a re-evaporator accumulator is used at the suction outlet of the evaporator on these systems, so the liquid that condenses in the coil during defrost doesn't go straight back to the compressor.
Reverse cycle (two-pipe) systems
A reverse cycle system uses the normal two pipes and runs the refrigerant backwards during defrost.
- A reversing valve (HTPG calls it a changeover valve) in the compressor discharge line sends hot gas down the suction line to the evaporator.
- A check valve in the suction line sends the gas through the drain pan loop first.
- The gas leaves the loop, enters the coil through a check valve assembly and gives up its heat, condensing to liquid.
- The liquid leaves at the distributor side, bypasses the TXV through a check valve and goes into the system liquid line, where it feeds the evaporators that are still cooling.
Heatcraft notes these systems usually have several evaporators on one condensing unit, and generally no more than one-third of the evaporators defrost at the same time.
Alternating evaporator systems
Here the hot gas line is taken off the compressor discharge line and piped with solenoids to each evaporator, so one or more evaporators defrost while the rest keep refrigerating. The liquid from the defrosting coils goes back into the main liquid line.
Heatcraft's warning: no more than 25% of the operating refrigeration load can be in defrost at any time, so that at least 75% of capacity keeps running to make the hot gas and offset the load of the coils in defrost.
Thermobank coils (Kramer)
HTPG's Thermobank coils have the solenoids and check valves factory-installed. In refrigeration the liquid line solenoid is open to feed the TXV. During defrost the liquid solenoid closes and the hot gas solenoid opens, feeding warm refrigerant to the coil and drain pan. When defrost reaches its termination pressure, normal operation resumes.
Piping rules
| Item | Heatcraft | HTPG |
|---|---|---|
| Expansion valve | Externally equalized. Bulb on a horizontal run of suction line close to the suction header, strapped tight line-to-line. | Size lines per ASHRAE for the conditions and refrigerant. |
| Suction line slope | 1 inch per 10 feet toward the compressor | 1/8 inch per foot toward the compressor |
| Risers | Trap vertical risers over 4 feet with a P-trap at the bottom; if a P-trap is used, put the TXV bulb between the unit and the trap | Trap risers over 5 feet with a P-trap at the bottom; inverted traps as needed into horizontal runs |
| Hot gas line size | Follow industry guidelines | Follow the piping figures for the system type |
On freezers, HTPG says the drain line inside the refrigerated space must be wrapped with heat tape and insulated so it doesn't freeze during defrost. The drain should be at least 1-1/4 inches with at least 1/2 inch of slope per foot, and trapped outside the box.
Start-up checks
From HTPG's start-up procedure:
- Pour water into the drain pan and confirm the pan and line empty completely; make sure the drain line is trapped, heated and insulated where needed.
- Verify the TXV gets a full column of liquid and set superheat. HTPG's factory recommendation is 6°F for standard applications.
- On first start, the fans won't run until the coil pulls down to about 25°F, and may cycle a few times until the room comes down.
- Expect a heavy frost load during pull-down; manual defrosts may be needed until the moisture level drops.
- Watch the first defrost cycle to confirm every valve, the termination and the fan delay work.
When the coil won't clear
Work from the schedule to the valves:
- Schedule and termination. HTPG says to check at least once a month for proper defrosting and that the defrost schedule may need changing for the box's room temperature, product, door traffic and humidity. Too few defrosts, a termination set too low or a fail-safe that's too short all leave frost behind.
- Is hot gas getting there? Feel the hot gas line and the pan loop during defrost. A cold line points to the hot gas solenoid (three-pipe and alternating), the reversing or changeover valve (reverse cycle), or the defrost control not calling.
- Is there enough load to make hot gas? On alternating and reverse cycle systems the coils still refrigerating supply the heat. Too many coils in defrost at once, or a nearly idle system, leaves too little hot gas. That's the reason for the 25% and one-third rules above.
- Check valves. The reverse cycle path depends on check valves in the suction line and around the TXV. As general practice, a valve stuck shut blocks the defrost path and one leaking through lets refrigerant take the wrong path; compare line temperatures on each side of the valve in defrost and in refrigeration.
- Pan ice but a clear coil. Pan loop not getting gas, unit not pitched toward the drain, plugged drain, or a drain line heater that's failed (HTPG's troubleshooting chart lists all four for ice in the drain pan).
- Fans not restarting after defrost. Heatcraft's fan delay control keeps the fans off until the coil is back below about 35°F (it closes at 35°F and opens at 55°F on its electric-defrost units). HTPG lists a defrost thermostat that isn't sensing coil temperature as a cause of fans not running. Check the control and that its sensor is mounted where it belongs.
Common mistakes
- Putting too much of the load into defrost at once. Heatcraft's limit is 25% of the operating load on alternating systems.
- Mounting the TXV bulb below a P-trap. Heatcraft says the bulb goes between the unit and the trap.
- Skipping the first-defrost check. Most piping and control mistakes show up the first time the system defrosts.
- Treating hot gas like electric defrost. There's no heater to test; the "heater" is the refrigerant path, so trace the gas.
FAQ
What's the difference between three-pipe and two-pipe hot gas defrost?
Three-pipe adds a dedicated hot gas line from the compressor discharge to each evaporator, fed through a hot gas solenoid. Two-pipe (reverse cycle) uses a reversing or changeover valve to send hot gas back down the suction line, with check valves routing it through the pan loop and around the TXV.
How many evaporators can defrost at once?
Heatcraft says no more than 25% of the operating refrigeration load on an alternating evaporator system, and generally no more than one-third of the evaporators on a reverse cycle system.
Why does a hot gas unit cooler have a pan loop?
The hot gas runs through the loop in the drain pan before the coil so the melted frost doesn't refreeze in the pan.
Related
- Walk-in cooler and freezer troubleshooting (electric defrost, superheat, drain lines)
- Walk-in condensing unit maintenance and cold-weather problems
- TXV troubleshooting
Sources
- Heatcraft, Unit Coolers Installation and Operations Manual (H-IM-UC, 2020): defrost troubleshooting p. 4, hot gas defrost systems and piping p. 7
- HTPG, Medium Profile, Heavy Duty and Warehouse Unit Coolers Installation and Operations Manual (HT-ML-IOM-0221B): drain line, piping and hot gas piping p. 7, start-up and maintenance p. 22, troubleshooting chart p. 24
- Heatcraft, Chandler low profile unit cooler technical guide: hot gas loop on bottom of coil
Was this guide useful?
One field tip a week
A short, practical HVAC tip in your inbox every week: diagnostics, charging, airflow and code changes. Free, unsubscribe anytime.
We'll only use your email for the newsletter. Privacy policy.
Related guides
Walk-In Cooler and Freezer Troubleshooting: Defrost, Superheat and Iced Coils
How a walk-in cooler or freezer runs and defrosts, the superheat targets at the evaporator and the compressor, how to set the defrost fail-safe, drain line rules for freezers, and what to check for a warm box, an iced coil, ice on the ceiling or a frozen drain pan, following Heatcraft's unit cooler and condensing unit manuals.
Walk-In Condensing Units: Preventive Maintenance and Cold-Weather Problems
The quarterly, semi-annual and annual maintenance Heatcraft lists for air-cooled walk-in condensing units, what to check when a unit short cycles or won't hold head pressure in cold weather, pressure fan cycling settings, and the extra rules for A2L condensing units.
Rooftop Unit Start-Up: Three-Phase Voltage, Compressor Rotation and the Checks That Matter
What to check when you start up a packaged rooftop unit - three-phase voltage imbalance (2% limit) and how to calculate it, scroll compressor rotation, the 208-volt transformer tap, condensate trap, gas pressure testing and the readings to record, following Carrier's rooftop unit instructions.
TXV Troubleshooting: Starving, Flooding and Hunting Expansion Valves
How to tell if a thermostatic expansion valve is really bad, using superheat and subcooling, and what to check first: bulb mounting, equalizer, liquid line, charge and airflow.
Field reference for trained technicians. Always follow the equipment manufacturer's instructions, local code and safe work practices. See our editorial standards, or report a correction.