Demand Controlled Ventilation (DCV) on Rooftop Units: CO2 Setpoints, VENTMIN/VENTMAX and Testing
A rooftop unit's outdoor air damper is usually set for the building at full occupancy. Most of the day the space has far fewer people in it, so the unit spends energy heating and cooling outdoor air nobody needs. Demand controlled ventilation (DCV) fixes that by reading CO2 in the space, which rises with the number of people breathing in it, and opening the outdoor air damper only as far as that number calls for. California's acceptance test guide describes it as reducing outdoor air below design values when the space is below design occupancy, with CO2 as the indicator of occupancy.
This guide follows the same two controllers as the economizer troubleshooting guide: Honeywell's JADE W7220 (sold by Carrier as EconoMi$er X and found on many other brands) and Carrier's EconomizerONE on 50FE units.
What a DCV setup includes
- A CO2 sensor in the space. On the JADE, either an analog 2-10 Vdc sensor or a wall-mount Sylk bus TR40.
- The economizer controller, which compares the CO2 reading with its DCV setpoint.
- Two damper positions instead of one. Without a CO2 sensor, the controller has a single minimum position (MIN POS). Once a sensor is connected, MIN POS disappears from the JADE menu and VENTMIN and VENTMAX take its place.
How it works
| Setting | What it is | JADE default |
|---|---|---|
| DCV SET | CO2 setpoint for the space | 1100 ppm (500 to 2000, in steps of 100) |
| VENTMIN | Damper position for the ventilation needed at less than full occupancy (Va) | 2.25 V |
| VENTMAX | Damper position for full design ventilation (Vbz); the same setting MIN POS would be without a CO2 sensor | 2.8 V |
| Two-speed fans | Separate VENTMIN L/H and VENTMAX L/H | VENTMIN L 2.5 V, H 2.25 V; VENTMAX L 3.2 V, H 2.8 V |
Positions are set in volts to the actuator (2 to 10 Vdc). With outdoor, mixed, return air and CO2 sensors all connected and DCV CAL ENABLE set to AUTO, the JADE can show and control them in CFM (100 to 9,990) instead; Honeywell says that automatic mode doesn't work on two-speed fan units.
Honeywell's sequence of operation tables (dry bulb or enthalpy, single-speed fan, occupied):
| CO2 | Outdoor air good to economize? | Damper |
|---|---|---|
| Below setpoint | No | VENTMIN |
| Below setpoint | Yes, with a cooling call | VENTMIN to fully open |
| Above setpoint | No | VENTMIN to VENTMAX |
| Above setpoint | Yes, with a cooling call | VENTMIN to fully open |
Unoccupied, the damper stays closed unless the unit is economizing. Carrier's EconomizerONE works the same way: as CO2 rises above the setpoint, the damper's minimum position increases in proportion until it reaches the maximum ventilation setting, and when the economizer is free cooling the damper follows whichever demand is higher. Carrier adds that DCV is disabled if the controller gets no occupancy signal.
Settings: the 1100 ppm default and the code
Both manuals ship with an 1100 ppm DCV setpoint. That may not meet the code where you are. California's 2025 acceptance test (NRCA-MCH-06-A) requires the setpoint to be no more than 600 ppm above outdoor CO2 when outdoor CO2 is measured, or no more than 1,000 ppm if there's no outdoor sensor. The code allows outdoor CO2 to be taken as 400 ppm without measuring it, measured continuously, or measured once at checkout.
California also requires DCV on spaces with a design occupancy of 40 square feet per person or less served by a system with an economizer, modulating outdoor air control, or more than 3,000 CFM of design outdoor air, with exceptions for small spaces (under 150 ft² or fewer than 10 people), spaces with high exhaust and spaces with uncaptured dust or fumes. Other states follow their own energy code.
Sensor setup on the JADE:
- With a C7632 or any 0-10 Vdc CO2 sensor, set CO2ZERO to 400 ppm and CO2SPAN to 1600 ppm in the Advanced Setup menu.
- A TR40 CO2 sensor on the Sylk bus must be set to address 6. Only one TR40 CO2 sensor can be used.
- DCV STATUS on the status menu shows ON above the setpoint and OFF below it.
Sensor placement and accuracy
California's acceptance criteria give a good field standard even outside California:
- Mount each CO2 sensor in the space, 3 to 6 feet above the floor.
- No more than one sensor per 10,000 ft² of space.
- Each sensor factory calibrated (with a certificate) or field calibrated, accurate to ±75 ppm at 600 and 1,000 ppm.
- If a sensor fails, the system resets to supply the minimum outside air at the levels in the approved design.
- A minimum outdoor air setting is provided whenever the system is occupied, regardless of CO2.
Testing DCV
California's test is done by a certified acceptance test technician, but the functional check is the same one any tech can use to see whether DCV works:
- Lock out the economizer so its logic doesn't move the damper during the test.
- Raise CO2 at the sensor slightly above the setpoint (calibrated gas, or the controller's simulated signal). The damper should modulate open toward VENTMAX.
- Drop the signal well below the setpoint. The damper should modulate closed to VENTMIN.
- Restore the economizer and sensor settings.
California's guide suggests two people on rooftop units, one at the sensor and one watching the damper. In cold weather, the damper opening during the test can put cold air across the coils: take care to keep them from freezing.
Troubleshooting DCV
| Problem | Check |
|---|---|
| No VENTMIN or VENTMAX in the menu | The controller doesn't see the CO2 sensor: wiring, signal type, or the TR40 address (must be 6) |
| CO2 SEN ALARM | Sensor failed, out of range or disconnected; see the economizer alarms |
| Damper never opens past VENTMIN | CO2 is below the setpoint, the setpoint is set too high, or (Carrier) there's no occupancy signal so DCV is disabled |
| Reading looks wrong | 0-10 V sensor scaling: on the JADE, CO2ZERO 400 and CO2SPAN 1600. Compare with a handheld reference probe |
| Too much outdoor air all the time | VENTMIN set too high, or the damper doesn't close fully; check minimum positions before blaming the sensor |
| Damper doesn't move at all | Drive it with the controller's checkout test; if it won't move under test, it's the actuator, wiring or linkage |
FAQ
What is demand controlled ventilation?
A control that varies outdoor air with occupancy, using CO2 in the space as the measure of how many people are there. Below the CO2 setpoint the damper holds a minimum ventilation position; above it, the damper opens toward full design ventilation.
What CO2 setpoint should DCV use?
Honeywell's JADE and Carrier's EconomizerONE default to 1100 ppm. California requires 1,000 ppm or less without an outdoor CO2 sensor, or no more than 600 ppm above outdoor CO2 when outdoor air is measured. Follow the energy code that applies to the building.
What are VENTMIN and VENTMAX?
The two damper positions a JADE economizer uses once a CO2 sensor is connected. VENTMIN is the ventilation needed at low occupancy (Va); VENTMAX is full design ventilation (Vbz) and replaces the single MIN POS setting. JADE defaults are 2.25 V and 2.8 V.
Where should a CO2 sensor be mounted for DCV?
In the space it controls, 3 to 6 feet above the floor, with no more than one sensor per 10,000 ft² (California's acceptance criteria).
Sources
- Honeywell JADE Economizer Module (W7220) Installation Instructions 63-2700-11, distributor-hosted copy: CO2 sensor p. 1, CO2ZERO/CO2SPAN and TR40 address p. 8, DCV STATUS p. 19, DCV SET, MIN POS, VENTMAX and VENTMIN p. 21, DCVCAL ENA p. 23, Table 6 and sequence of operation pp. 26-27
- Carrier 50FE 08-14 Installation Instructions, EconomizerONE: multi-speed fan and DCV damper positions pp. 39-40
- California Energy Commission, 2025 NRCA-MCH-06-A Quick Reference: Demand Control Ventilation Systems
- California Energy Commission, 2025-CEC-NRCA-MCH-06-A certificate of acceptance (sensor accuracy and spacing)
Was this guide useful?
One field tip a week
A short, practical HVAC tip in your inbox every week: diagnostics, charging, airflow and code changes. Free, unsubscribe anytime.
We'll only use your email for the newsletter. Privacy policy.
Related guides
Rooftop Unit Economizers: How They Work, Setup and Troubleshooting
How a packaged rooftop unit economizer decides when to use outdoor air, the factory default setpoints on Carrier EconomizerONE and Honeywell JADE W7220 controllers, how to run the built-in checkout tests, what each fault alarm means, and what to check when free cooling isn't working.
Rooftop Unit Start-Up: Three-Phase Voltage, Compressor Rotation and the Checks That Matter
What to check when you start up a packaged rooftop unit - three-phase voltage imbalance (2% limit) and how to calculate it, scroll compressor rotation, the 208-volt transformer tap, condensate trap, gas pressure testing and the readings to record, following Carrier's rooftop unit instructions.
Intermittent Pilot Ignition Troubleshooting: Honeywell S8610U Sequence, LED Codes and Checks
How an intermittent pilot (spark-to-pilot) system works and how to troubleshoot it on older furnaces and boilers, using the Honeywell/Resideo S8610U as the example. Sequence of operation, LED flash codes, the arc test, flame current and what to check for no spark, no pilot, spark that won't stop and a main valve that won't open.
Furnace Inducer Motor: Testing, Noises and When It's Really the Pressure Switch
Signs of a bad furnace draft inducer motor, how to test one that won't start, runs noisy or won't prove the pressure switch, and how to tell it from a vent or pressure switch problem.
Field reference for trained technicians. Always follow the equipment manufacturer's instructions, local code and safe work practices. See our editorial standards, or report a correction.