Air in a Hot-Water Heating System: Purging, Air Separators and Vents
Air is behind a lot of hydronic complaints: a zone that won't heat, gurgling and rushing noises, a circulator that runs but doesn't move water, and boilers that short cycle. Getting it out and keeping it out comes down to purging properly and having the right parts in the right places.
This guide follows Taco's technical article Air Elimination from Hydronic Heating Systems (TD11) and Taco's instruction sheets for its air separators and Hy-Vent air vents.
Safety: Boiler water can be scalding and under pressure. Shut the boiler off and let it cool before opening purge valves or vents. This is work for a trained technician.
What air does
Taco lists four problems:
- No flow: air pockets can block flow through parts of the system (air binding).
- Poor pump performance: a water-air mix is compressible, so the circulator works less efficiently.
- Noise: water tumbling through pipes that hold air.
- Corrosion: dissolved oxygen attacks steel and iron parts.
Two kinds of air
- Bulk air fills the piping when the system is new or has been drained. Purging removes it.
- Dissolved air. Taco notes that cold water at 50°F and 50 psi can hold up to 10% dissolved gas by volume. As the water heats, the gas comes out as tiny bubbles, mostly on the inside of the boiler heat exchanger. A central air separator collects it over the first days of operation.
Purging bulk air
Forced-water purging pushes water through the piping in one direction fast enough to drive the air ahead of it, out a drain valve.
Taco's typical setup:
- A full-port ball valve, shut during purging, and a drain valve with a hose to a drain, arranged so water flows through the distribution piping in one direction and out the drain.
- A make-up water assembly with isolation valves, backflow preventer, pressure-reducing valve and fast-fill, opened during purging.
Keep going until the water leaving the hose runs smooth with no visible bubbles.
Flow matters. Taco says you need at least 2 feet per second to carry bubbles along, especially where water flows down a vertical pipe and big bubbles can rise against it. Flow needed for 2 ft/s in type M copper:
| Copper tube | Flow for 2 ft/s |
|---|---|
| 3/4 in. | 3.2 gpm |
| 1 in. | 5.5 gpm |
| 1-1/4 in. | 8.2 gpm |
| 1-1/2 in. | 11.4 gpm |
| 2 in. | 19.8 gpm |
If the fill can't supply that much flow, bubbles can stay behind, especially in downward-flowing pipe.
The air separator: where it goes
Water gives up dissolved gas when it's hot and at low pressure. So Taco says to put the separator:
- After the boiler (hottest water), and
- Before the circulator, so the pump pumps away from it.
Taco's separators have a 1/2-inch tapping on the bottom for the diaphragm expansion tank, and make-up water usually connects there too. Taco's 4900 instruction sheet says to mount the separator as close as possible to the boiler outlet and upstream of the pumps.
Separator types (Taco):
- Air scoop: vanes steer bubbles up to a float vent. Keep entering velocity at or below 4 ft/s (for example, 6.5 gpm max in 3/4-inch copper, 10.9 gpm in 1-inch).
- Vortex type (VorTech): spins the water so air collects at the center and rises to the vent. About 4 ft/s is ideal; up to 10 ft/s works but separates less. Include its head loss when sizing the circulator.
- Coalescing type (4900 Series): stainless PALL rings catch microbubbles until they grow big enough to rise. Taco rates it for closed systems up to 240°F and 150 psi.
On a 4900 during the first fill, Taco says to close the separator's automatic vent (turn the orifice screw clockwise) so debris doesn't foul it, open the side flushing cock until water appears, then reopen the vent 1 to 1-1/2 turns. Open the flushing cock periodically to clear debris from under the vent.
High-point vents
Automatic float vents (Taco Hy-Vent) go wherever air collects, usually the highest points: tops of risers, and where pipe goes up over a beam. Taco says to:
- Install a stop valve under each vent so it can be replaced without draining.
- Clean the system before installing vents, since scale and debris make them leak.
- Not use them on steam or on systems with oil or petroleum additives.
Keep pressure up. Taco says system pressure at every vent should be at least 3 psi above atmospheric. Below that, a vent can pull air into the system, so a system with low pressure at the top floor keeps getting air back. Taco notes that pressure drops with height and with head loss along the circuit, so check it at the vents themselves (see boiler pressure and relief valve).
Troubleshooting air problems
| Symptom | Check |
|---|---|
| One zone cold, others fine | Purge that zone; check its zone valve opens |
| Gurgling or rushing water | Purge; check pressure at the highest vent is at least 3 psi |
| Circulator runs, no flow | Air in the pump; see boiler circulator not running |
| Air keeps coming back | Low pressure at high vents, a leaking vent, or no central separator |
| Boiler short cycles | Air or low flow; see boiler short cycling |
Related
- Hot-water boiler: no heat (guided troubleshooter)
- Zone valve troubleshooting
- Boiler circulator not running
- Boiler short cycling
Sources
- Taco, Air Elimination from Hydronic Heating Systems, TD11 (effective 08.03.2015): tacocomfort.com
- Taco, 4900 Series Air & Dirt Separators instruction sheet 402-080: tacocomfort.com
- Taco, 4900 Series Air Separators brochure 100-2.9: tacocomfort.com
- Taco, Hy-Vent Automatic Air Vent instruction sheet 102-583: tacocomfort.com
Was this guide useful?
One field tip a week
A short, practical HVAC tip in your inbox every week: diagnostics, charging, airflow and code changes. Free, unsubscribe anytime.
We'll only use your email for the newsletter. Privacy policy.
Related guides
Boiler Circulator Not Running: Power, Relay, Seized Cartridge or Air Lock?
How to tell why a hydronic circulator pump isn't moving water - no power from the relay, a seized cartridge, or air in the pump - using Taco's own instructions for "00" circulators.
Boiler Short Cycling: Settings, Flow, Venting or an Oversized Boiler?
A checklist for a hot-water boiler that fires, shuts off and fires again every few minutes, based on IBC's cycling troubleshooting table for its condensing boilers. Covers control settings and differential, low water flow, air, venting and condensate, and boiler size.
Boiler Pressure Too High or Relief Valve Dripping: Expansion Tank and Fill Valve Checks
Why a hot-water boiler's pressure climbs until the relief valve weeps, and how to check the expansion tank precharge and the fill valve before replacing the relief valve.
Hot-Water Zone Valve Troubleshooting: Valve, Motor or End Switch?
How to find out why a hydronic zone gets no heat or won't shut off. Covers how a zone valve and its end switch start the boiler, what to measure, and how to tell a bad motor head from a stuck valve.
Field reference for trained technicians. Always follow the equipment manufacturer's instructions, local code and safe work practices. See our editorial standards, or report a correction.