Home / Guided troubleshooting / Hot-water boiler: no heat

Hot-water boiler: no heat: guided troubleshooting

One zone or the whole house is cold on a hydronic (hot-water) system. Answer each question from what you see on site.

Step 1

Is the whole house cold, or just one zone?

For trained technicians. Line voltage, gas and refrigerant work can injure or kill. Never jumper a safety switch to keep equipment running, and follow the manufacturer's instructions for the unit in front of you.
See every step in this flow
  1. Is the whole house cold, or just one zone?
    • Just one zone: With that zone's thermostat calling, is there 24 V at its zone valve (or zone circulator relay)?
    • The whole house: Is the boiler firing and getting hot?
  2. With that zone's thermostat calling, is there 24 V at its zone valve (or zone circulator relay)?
    • No: No call reaching the zone
    • Yes: Does the zone valve open, and does the boiler get a call?
  3. Does the zone valve open, and does the boiler get a call?
    • Valve doesn't open: Zone valve motor head
    • Valve opens, boiler gets no call: End switch
    • Both happen, pipe past the valve stays cold: Air in the loop
  4. Is the boiler firing and getting hot?
    • No: The boiler isn't firing
    • Yes: Is the circulator running?
  5. Is the circulator running?
    • No, or it hums: Circulator
    • Yes: What does the pressure gauge read cold?
  6. What does the pressure gauge read cold? Compare with the fill pressure on the fill valve or in the system's documents; many residential systems fill to about 12 psi.
    • Low, near zero: Low system pressure
    • Normal: Air in the loop
    • High, relief valve dripping: Pressure too high

Where each path ends

No call reaching the zone

Check the thermostat, its batteries or C wire, the cable, and the transformer or zone panel feeding that valve.

Zone valve motor head

24 V at the valve and it doesn't open means the motor head has failed. On many valves the head can be replaced without draining.

End switch

The end switch closes at the end of the opening stroke and calls the boiler. If it doesn't close, the head or switch is bad. Jumper the end switch to test, never the 24 V motor coil.

The boiler isn't firing

Check the boiler's own display or LED codes, the aquastat or high limit, and gas or oil supply. On a gas boiler the ignition and flame sensing work much as they do on a furnace.

Circulator

Check for 120 V at the circulator on a call. With voltage and no rotation, the cartridge is likely seized or the motor has failed.

Low system pressure

Low pressure lets air into the high points and starves the loop. Find out why it dropped (a leak, or a relief valve that has been discharging), then refill to the fill pressure and purge.

Pressure too high

Usually a waterlogged expansion tank or a fill valve passing water. Fix the cause before replacing the relief valve.

Air in the loop

Purge the zones one at a time with the purge valves, and run the circulator for a few minutes after refilling to clear air from its bearing chamber. Check that isolation valves and any flow check are open.