Home / Tools / Refrigerant

TXV Sizing Calculator

Pick the refrigerant, valve type and evaporator temperature, enter the load, liquid temperature and pressure drop, and the tool corrects every size in Sporlan's capacity table to your conditions and picks the smallest one that covers the load.

tons
°F
°F
psig
psig
psi

Enter the lowest condensing temperature or pressure, or switch to entering the pressure drop directly.

Sporlan's recommended thermostatic charges for R-410A: air conditioning ZGA, ZCP180; commercial refrigeration (+50 to −10°F) none listed; low temperature (0 to −40°F) ZZP55.

Capacity = table rating × CF liquid temperature × CF pressure drop (Sporlan Bulletin 10-10, p. 67), using the "R410A and like refrigerants" pressure drop table. Correction factors between Sporlan's columns are interpolated. Ratings assume vapor-free liquid at the valve: flash gas from too little subcooling cuts capacity no matter what size you pick.

How Sporlan sizes a TXV

Sporlan's selection procedure (Bulletin 10-10, p. 65) works in this order:

  1. Liquid temperature entering the valve. The tables are rated at 100°F vapor-free liquid. Colder liquid (more subcooling) raises capacity; warmer liquid lowers it. The correction factor comes from Sporlan's table for each refrigerant.
  2. Pressure drop across the valve. Start with condensing pressure minus the evaporating pressure at the design evaporator temperature. Use the lowest condensing pressure the system runs at. Then subtract every other loss: liquid line and evaporator friction, the drier and solenoid, vertical lift in the liquid line, and the distributor.
  3. Pick from the capacity table. Choose a valve whose corrected capacity equals or slightly exceeds the design load. On systems with more than one evaporator, size each valve for its own evaporator.
  4. External equalizer. Sporlan says an externally equalized valve must be used on evaporators with a refrigerant distributor, and should always be used with air conditioning thermostatic charges.
  5. Body and charge. Pick the body for the connections, then the thermostatic charge for the evaporator temperature (listed under the calculator for each refrigerant).

Corrected capacity = table rating × CF liquid temperature × CF pressure drop. The table ratings use a maximum opening superheat of 7°F and a standard factory superheat setting; Sporlan says the 40°F, 20°F, −10°F and −40°F ratings follow AHRI Standard 750.

Worked example (Sporlan's numbers)

Sporlan's own example: R-22, medium temperature, 20°F evaporator, 1 ton. Condensing 182 psig minus evaporating 43 psig is 139 psi. Take off 4 psi for the liquid line and accessories and 35 psi for the distributor and tubes, and 100 psi is left across the valve. With 70°F liquid:

  • EG 1-ton rating at 20°F: 1.09 tons
  • CF liquid temperature, R-22 at 70°F: 1.18 (the bulletin's worked example prints 1.17; its current correction table lists 1.18)
  • CF pressure drop, 100 psi at 20°F: 0.89
  • Capacity: 1.09 × 1.18 × 0.89 = 1.14 tons, so the 1-ton EG covers the 1-ton load.

Mistakes this catches

  • Swapping R-410A valves onto R-32. Sporlan keeps the same Z refrigerant code and nomenclature for both, but its R32 addendum (Bulletin 10-10-12) says the same valve has 36% to 46% more capacity on R-32. A valve stamped 2 tons is about a 3-ton valve on R-32 (3.98 vs 2.72 tons at 40°F).
  • Assuming an R-454B size means the same thing. R-454B valves have their own size steps (1/2, 3/4, 1, 1 1/2, 2 1/2, 3, 4 1/2, 6 and up) under the Y code.
  • Ignoring the distributor. In Sporlan's example the distributor and tubes take 35 psi of the 139 available. Leave it out and the valve looks bigger than it is.
  • Sizing off summer head pressure. Sporlan says to use the minimum operating condensing pressure. A valve that's fine at 100°F outdoor can starve the evaporator at a low head pressure setting in winter.
  • Heat pumps. Sporlan's residential section says heat pumps need a check valve so refrigerant can flow backward through the inactive valve. RC, HXC and FXC valves have internal check valves good for about 6 tons on R-410A; larger systems need an external check valve.

Which valves are approved for A2L refrigerants

Sporlan's air conditioning table (p. 5) lists ER, EBQ, RC and HXCAE as A2L/A3 approved for residential and heat pump use, and ER and O for commercial air conditioning. Their nominal ranges:

ValveR-410A (Z)R-32 (Z)R-454B (Y)Internal check valve
ER1/3-151/2-211/2-18No
EBQ1/3-61/3-51/2-7No
RC1-61-1/2-101-8.5Yes
HXCAE2-83-1/2-123-10Yes
O (commercial)20-6029-8520-70No

BBI and CBBI are OEM-only valves (Sporlan lists BBI as equivalent to the ER and CBBI as equivalent to the RC); they share capacity tables with those valves.

Recommended thermostatic charges

RefrigerantAir conditioningCommercial refrigeration (+50 to −10°F)Low temperature (0 to −40°F)
R-410AZGA, ZCP180none listedZZP55
R-454BYCPnone listednone listed
R-32ZGA, ZCP180none listedZZP55
R-22NGA, VCP100VCVZ, VZP40
R-404ASCP115SC, PCSZP
R-448Anone listedVCVZ, VZP, VZP40
R-134aJCP60JCJZ, JZP

Sporlan's note: for dual temperature applications use the C charge; the VC and SC charges can be used down to −30°F. For HX and FX valves Sporlan recommends KX, KXB, ZX and ZXB charges.

What's not in the tool

  • Large commercial bodies (H, M, V, W), NX balanced-port valves and other refrigerants in the bulletin. Use Sporlan's tables or its Virtual Engineer program.
  • Evaporator temperatures between Sporlan's columns. Pick the nearest column; Sporlan says to contact them for conditions not in the tables.
  • A few printed rows that can't be tied to a size (duplicate labels in the R-404A O, R-448A O and R-448A EF tables). The calculator notes them where they apply.

Related: TXV troubleshooting, superheat and subcooling calculator, R-32 vs R-454B, low pressure control settings.

Sources

  • Sporlan Division, Parker Hannifin, Bulletin 10-10, Thermostatic Expansion Valves with Selective Thermostatic Charges (October 2026): selection procedure p. 65, capacity table notes and recommended thermostatic charges p. 66, liquid temperature and pressure drop correction factors p. 67, capacity tables pp. 69-87, air conditioning valve table p. 5. Read from the printed tables.
  • Sporlan, Bulletin 10-10-12, R32 TEV Sizing Addendum (April 2026): same Z code for R-410A and R-32, 36-46% more capacity on R-32.

Related tools

Results are estimates for field reference. Always confirm against the equipment manufacturer's charging chart, installation instructions and local code. Found a problem with this tool? Tell us.