Recovery Cylinder Fill Calculator
Find the most a recovery cylinder should weigh on the scale for the refrigerant you're recovering, and whether the charge you're about to pull will fit.
How it works
Max scale weight = (0.8 × WC × SG) + TW
- WC is water capacity: the pounds of water that would fill the cylinder completely. It's stamped on the collar.
- SG is the specific gravity of the liquid refrigerant at 77°F. Refrigerants are not the same density as water, so the same cylinder holds a different weight of each one.
- 0.8 leaves 20% of the cylinder for the liquid to expand as it warms.
- TW is tare weight, the empty cylinder. The scale reads cylinder plus refrigerant, so it has to be added back.
This is the AHRI Guideline K formula, as printed by cylinder maker Worthington and by refrigerant maker Arkema. Example: a cylinder stamped WC 47.7 and TW 28.2, recovering R-410A (SG 1.06): 0.8 × 47.7 × 1.06 + 28.2 = 68.6 lb on the scale.
Before you recover
- Weigh the cylinder first. A cylinder that already holds refrigerant has less room than its label size suggests.
- R-454B and R-32 are lighter than R-410A, so the same cylinder holds fewer pounds of them.
- Use a cylinder rated for the refrigerant. Arkema lists R-410A only for 400 psig cylinders.
- Don't mix refrigerants in one cylinder, and check the cylinder's test date.
- Hoses and fittings hanging on the cylinder add weight to the scale reading.
Where the specific gravities come from
Most values are from Arkema's Forane reclaim cylinder table (specific gravity at 77°F). R-454B and R-32 are not in that table: we worked them out from published liquid density at 77°F (the Solstice R-454B data sheet, 61.47 lb/ft³; a supplier data sheet for R-32, 0.9588 kg/L) and rounded down, which keeps the limit on the safe side. If the refrigerant maker gives a different figure, choose "Other" and enter it.
Related: the EPA 608 Core study guide and the refrigerant service log.
Sources
Was this tool useful?
One field tip a week
A short, practical HVAC tip in your inbox every week: diagnostics, charging, airflow and code changes. Free, unsubscribe anytime.
We'll only use your email for the newsletter. Privacy policy.
Related tools
Superheat & Subcooling Calculator
Enter your line temps and saturation temps; get superheat and subcooling instantly.
TSHTarget Superheat Calculator
Target superheat for piston and cap-tube systems from indoor wet bulb and outdoor dry bulb.
PSIGLow Pressure Control Settings
Sporlan's cut-out and cut-in for coolers, meat cases and freezers on R-448A, R-454B, R-22 or R-513A, with the saturation temperature behind each, and how far off your current settings are.
Results are estimates for field reference. Always confirm against the equipment manufacturer's charging chart, installation instructions and local code. Found a problem with this tool? Tell us.