Target Superheat Calculator

For piston and cap-tube systems. Enter indoor wet bulb and outdoor dry bulb to get the target superheat.

°F WB
°F DB
°F
Target superheat
–

How it works

Target superheat = ((3 × indoor wet bulb) − 80 − outdoor dry bulb) ÷ 2

This is the formula behind the superheat charging charts that ship with fixed-orifice equipment. The charts cover indoor wet bulb from about 50 to 76 °F and outdoor dry bulb from about 55 to 115 °F. When the target comes out below 5 °F, the chart leaves that box blank: don't charge by superheat, weigh in the charge instead.

Getting good readings

  • Indoor wet bulb: measure return air at the evaporator, not at a grille across the house.
  • Outdoor dry bulb: measure air entering the condenser coil, in the shade.
  • Check airflow first. Low airflow pushes superheat down and makes an undercharge look correct.
  • Do not use this target on TXV or EEV systems; charge those by subcooling with the superheat & subcooling calculator.