Refrigerant Leak Rate Calculator (AIM Act)
Since January 1, 2026, the leak repair rules cover appliances with 15 lb or more of an HFC refrigerant. Enter the appliance, the refrigerant and what you added. The calculator tells you whether the rule applies, works out the leak rate the way EPA specifies, and if it's over the limit, gives the repair, verification and inspection deadlines.
The two EPA methods
A leak rate has to be calculated every time refrigerant is added to a covered appliance. The owner can use either of two methods, but the same method must be used for every covered appliance at a facility.
Annualizing: leak rate = (lb added ÷ lb full charge) × (365 ÷ shorter of days since the last addition or 365) × 100
Rolling average: leak rate = (lb added in the past 365 days, or since the last successful follow-up verification test if sooner) ÷ lb full charge × 100
The annualizing method projects one top-off to a full year, so a small addition made soon after the last one can come out high. The rolling average adds up what actually went in over the past year. For the first annualizing calculation after January 1, 2026, the rule says to use 365 days as the time since the last addition. For the first rolling average calculation, count only what was added since January 1, 2026.
Worked example
A walk-in cooler condensing unit with an 18 lb charge of R-448A (commercial refrigeration, 20% threshold) takes 3 lb, 90 days after the last top-off:
3 ÷ 18 × 365 ÷ 90 × 100 = 67.6% per year
That's over 20%, so the 30-day repair clock starts on the day the 3 lb went in.
Does the rule apply?
| Situation | Leak repair rule |
|---|---|
| 15 lb or more of an HFC or HFC blend (R-410A, R-454B, R-32, R-134a, R-404A, R-448A and others) | Covered by 40 CFR 84.106, from January 1, 2026 |
| Residential and light commercial AC and heat pumps | Exempt |
| Refrigerant with no HFC and a GWP of 53 or below (R-290, CO2, ammonia, HFOs) | Not covered |
| Only R-22 or another ozone-depleting refrigerant | Section 608 rule instead, at 50 lb or more |
Is a rooftop unit "light commercial"?
The regulation's definition of comfort cooling names packaged rooftop units, chillers and commercial split systems as examples, so a rooftop unit with 15 lb or more of an HFC is covered unless it belongs to the exempt residential and light commercial subsector. EPA describes that subsector as equipment that cools individual rooms, single-family homes and small commercial buildings, and says chillers and some VRF systems belong to their own subsectors. It hasn't defined "light commercial" in the regulation itself, and the trade press has reported confusion over where the line falls. A rooftop unit on a small strip-mall tenant space and a large unit on a mid-size office building may land on different sides. When it's unclear, the building owner should make that call with EPA's guidance, not the tech on the roof.
Thresholds
- 10%: comfort cooling, refrigerated transport and other appliances
- 20%: commercial refrigeration
- 30%: industrial process refrigeration
What happens when it's over
- Repair within 30 days of the addition (120 days if an industrial process shutdown is needed). A certified technician must do the leak inspection and the repair.
- Initial verification test on each repaired leak within the same window.
- Follow-up verification test within 10 days of a successful initial test.
- Annual leak inspections (quarterly for commercial or industrial process systems of 500 lb or more) until the leak rate stays under the threshold for a year, or four quarters in a row.
- If it still leaks above the threshold after the repairs, a retrofit or retirement plan within 30 days, with the work done within a year.
- If 125% or more of the full charge leaks out in a calendar year, a chronic leaker report to EPA by March 1 of the next year.
Most of these duties fall on the equipment owner or operator, but EPA says certified technicians must comply too, and in practice the contractor is the one with the scale and the numbers. Records must be kept for at least three years, and the full charge record until three years after the appliance is retired.
Log every visit on the free refrigerant service log. For the rest of the 2026 rules, see HFC rules in 2026: what the AIM Act means for HVAC techs.
This calculator is a field aid, not legal advice. EPA has said it will reconsider parts of its HFC rules, including leak management, so check the current regulation before relying on a date.
Sources
Was this tool useful?
One field tip a week
A short, practical HVAC tip in your inbox every week: diagnostics, charging, airflow and code changes. Free, unsubscribe anytime.
We'll only use your email for the newsletter. Privacy policy.
Related tools
Superheat & Subcooling Calculator
Enter your line temps and saturation temps; get superheat and subcooling instantly.
TSHTarget Superheat Calculator
Target superheat for piston and cap-tube systems from indoor wet bulb and outdoor dry bulb.
80%Recovery Cylinder Fill Calculator
Water capacity, tare weight and refrigerant in; the most the scale should read and how many pounds of room are left out.
Results are estimates for field reference. Always confirm against the equipment manufacturer's charging chart, installation instructions and local code. Found a problem with this tool? Tell us.