Rheem and Ruud EcoNet Zoning: Wiring, Start-Up and Common Alerts

EcoNet zoning is not a standard zone panel that switches thermostat wires. The EcoNet Smart Thermostat runs the equipment and the zoning together over the communicating bus, so wiring mistakes and skipped start-up tests cause most of the problems.

This guide follows Rheem's installation instructions for the EcoNet Zoning Panel by EWC Controls (part REPNL700ZON, form 92-106930-06). The newer 800 series (REPNL800ZON with the ETST800SYS thermostat) has its own instructions, so use those if that's what's on the wall.

Safety: Shut off power to the indoor unit before wiring the panel, dampers or bus. Zoning setup on communicating equipment is work for a trained technician.

What's in the system

  • EcoNet Smart Thermostat (ETST700SYS): the master control. It must be the zone 1 thermostat.
  • EcoNet Zone Control (RECTL700ZON): one in each of zones 2 to 6. They don't have to run back to the panel; they can be daisy-chained to any device on the bus.
  • Zone panel (REPNL700ZON): handles three zones. Two panels give six zones. A DIP switch sets the second panel to zones 4-6. One housing holds both panels.
  • Dampers: EWC Ultra-Zone 24 VAC power-open/power-close modulating dampers (models URD, ND or SID), which position to one of 35 steps. Up to five dampers per zone, wired in parallel.
  • Equipment: EcoNet Enabled equipment with an ECM variable-speed (constant CFM) blower. Systems with a constant-torque (X13 type) blower are not supported. Rheem names the H2T series air handlers as an example.

No bypass damper, external transformer or leaving-air sensor is needed in most applications. The system watches airflow into each zone and adjusts to protect against coil freezing, limit trips and uncomfortable leaving-air temperatures.

Planning the zones

  • Every floor should be its own zone. Split floors further as needed.
  • Group rooms with similar use, occupancy and load.
  • Zone 1 should be the main and usually the largest zone.
  • Each zone should be able to take the minimum airflow of the equipment.

Wiring

The bus. Four wires: R, C, E1 and E2. Use ordinary thermostat wire, 18 AWG or larger. Keep each run between communicating controls under 125 feet, and the whole bus under 500 feet end to end. Run extra conductors in case one breaks, and label each wire at the panel end.

Wire it as a daisy chain, not a star: each device has one cable in and one out, except the two devices at the ends. The thermostat and the outdoor unit should always be at the ends.

Zone panel terminals:

Terminal Connect to
E1, E2 E1 and E2 of the EcoNet equipment
R, C R and C of the indoor unit, or an external 24 VAC transformer
RT Usually nothing. It's a communication ground and must not go to C of the indoor unit
Z1-Z3: PO, COM, PC Each zone's dampers: power open, common, power close

The RRS/RTN terminals and the IAQ relay (NO, COM, NC) are not used.

Shielded wire. If the bus runs near or alongside line voltage, cable TV, Ethernet or RF equipment, shielded thermostat wire helps. Tie all the shields together and ground them at the indoor unit only (C or ground). Don't connect a shield at the zone panel. Grounding a shield in more than one place creates current loops.

External transformer. Use a separate 24 VAC, 40 VA transformer if there are more than five dampers in total or two zone panels. Connect C from the indoor unit to the panels, but not R. The transformer must be in phase with the indoor unit's transformer: measure R to C at the panel. About 48 V means out of phase, so swap the transformer leads. Close to 0 V means in phase.

Panel location. A nearby wall or plywood between studs. Not on the supply or return duct, and not on the furnace, air handler or coil cabinet. Unconditioned attics, basements and crawl spaces are fine (the panel is rated -20 to 160°F, 0-95% RH non-condensing).

Reading the zone panel LEDs

  • LED 1: pulses green while data moves on the EcoNet bus.
  • LED 3: steady on/off green heartbeat means the processor is working.
  • LEDs 2, 4 and 6 (one per zone): solid green = damper fully open; solid red = fully closed; off = damper moving or in between.

No pulsing on LED 1 points at the bus wiring. A zone LED that never changes while that zone calls points at the damper or its wiring.

Start-up

  1. Power up. The thermostat runs its auto-configuration and finds the zone controls.
  2. Assign zone IDs. On each zone control: Menu > Settings > Zone ID Assignment.
  3. Check that every zone shows up. On the main thermostat: Menu > Status > Zoning lists each zone with set point, temperature, humidity, damper position and airflow. A missing zone means checking the wiring to that zone control.
  4. Make sure zoning is on. Menu > Settings > Zoning.
  5. Run Duct Measurement after the equipment is commissioned and any refrigerant charging is done: Menu > Service > Zoning Checkout, select Duct Measurement, Start Test. It closes all dampers to measure leakage, opens each zone in turn, then opens all of them to size each zone. Allow about a minute per zone. It repeats automatically once a week.
  6. Run Damper Linearization from the same menu. It steps each damper and learns how airflow changes, about five minutes per zone. Airflow through a damper isn't linear with position, so this gives steadier airflow and temperatures.

If Duct Measurement sees more than 1 inch of static pressure, it raises A004_S Static Pressure High. The equipment keeps running; the alert is telling you the ductwork or filter is too restrictive. See total external static pressure.

Intelligent bypass (optional)

Rheem recommends a bypass only when the smallest zone can't take the system's lowest capacity, and it's used as a last resort after blower reduction, capacity reduction and dumping into set-back zones.

  • It must be an EWC power-open/power-close modulating damper, not a spring or barometric bypass.
  • Wire it to the zone 6 output of the second panel and turn on DIP switch 2 (Bypass) on that panel. That leaves five controlled zones.
  • A leaving-air temperature sensor is required with a bypass, wired to the indoor unit's control board.

Common complaints and alerts

Registers too loud or blowing too hard. Lower the zone's Zone Airflow Limit while the zone is running: Menu > Settings > Zone Settings on the main thermostat, or Menu > Settings on the zone control. Airflow drops with each step. Use the highest setting that's comfortable.

T00x_Z Zone x Airflow Alert - Caused Shutdown (in the alarm history). That zone hit its airflow limit and the system shut down. Raise that zone's Zone Airflow Limit, or raise the Over-Conditioning setting for the other zones (Menu > Settings > Zone Settings on the main thermostat).

T007_Z Blower Cutback - Caused Shutdown. The blower couldn't reach the speed it needed because of duct restriction or too little open zone area. If any zone's airflow limit is set to Unlimited, change it to High, and check for a dirty filter.

Source

  • Rheem, EcoNet Zoning Panel by EWC Controls Inc. Installation Instructions, form 92-106930-06 (9/18), pp. 1-8: media.ruud.com

Related guides

Field reference for trained technicians. Always follow the equipment manufacturer's instructions, local code and safe work practices. See our editorial standards, or report a correction.