Thermostat Wiring: Terminal Letters and Wire Colors Explained
Thermostat terminals are fairly standard; wire colors are not. Wire by terminal, and confirm at the equipment end before you power up.
Terminal reference
| Terminal | Function | Common wire color |
|---|---|---|
| R | 24 VAC power from the transformer | Red |
| Rc / Rh | Separate 24 V supplies for cooling and heating (two-transformer systems). Jumpered together on most single-transformer systems | Red |
| C | 24 VAC common (return), needed to power most smart thermostats | Blue or black |
| W / W1 | Heat, first stage | White |
| W2 | Second-stage heat, or auxiliary heat on some heat pumps | Brown or other |
| Y / Y1 | Cooling (compressor), first stage. Also the compressor in heat pump heating | Yellow |
| Y2 | Second-stage compressor | Light blue or other |
| G | Indoor blower fan | Green |
| O | Reversing valve energized in cooling (most brands) | Orange |
| B | Reversing valve energized in heating (traditionally Rheem/Ruud). On some older systems, B is the common, so verify | Dark blue |
| E | Emergency heat (heat strips only, no compressor) | Varies |
| AUX | Auxiliary heat | Varies |
| L | Fault or service indicator from the heat pump | Varies |
Conventional system vs. heat pump
- Conventional (furnace + AC): R, C, W, Y, G. A call for heat closes R to W; a call for cooling closes R to Y and R to G.
- Heat pump: R, C, Y, G, O/B, plus W2/AUX/E for strips. Y runs the compressor in both heating and cooling, and O/B decides which mode. Getting O vs. B wrong swaps heating and cooling. See heat pump blowing cold air.
How to verify a hookup
- Before you disconnect anything, photograph the existing wiring at the thermostat and at the equipment.
- At the furnace or air handler board, follow each conductor to its terminal. Colors at the thermostat may not match colors at the equipment, especially on older installs.
- With power on, check 24 V between R and C at the thermostat.
- Test each call: jumper R to the terminal at the board briefly, or use the thermostat, and confirm the right equipment responds.
Don't short R to C. A short across the transformer secondary will blow the board's low-voltage fuse or damage the transformer.
No C wire?
Options include using a spare conductor in the existing cable, running new cable, or using an add-a-wire kit from the thermostat manufacturer. Avoid "power stealing" setups that make relays chatter or equipment short cycle.
FAQ
What does the C wire do?
It completes the 24 V circuit so a smart thermostat has continuous power. Without it, many thermostats try to steal power through other circuits.
Is the blue wire always C?
No. Blue is often used for C, but it's also used for B or second stages. Always verify by terminal.
Why are R and Rc jumpered?
On systems with a single transformer, the jumper sends the same 24 V to the heating and cooling circuits. Remove it only on systems with two transformers.
Sources
One field tip a week
A short, practical HVAC tip in your inbox every week: diagnostics, charging, airflow and code changes. Free, unsubscribe anytime.
We'll only use your email for the newsletter. Privacy policy.
Tools for this job
Related guides
AC Compressor Not Starting: Humming, Clicking or Nothing at All
Diagnose a compressor that won't start by what it does: humming points to capacitor or locked rotor, clicking to overload, silence to the control circuit.
Condenser Fan Not Spinning: Capacitor, Motor or Control?
Find out why an outdoor condenser fan won't run, from the fan capacitor and seized bearings to the contactor, wiring and heat pump defrost.
How to Test an AC Contactor: Coil, Contacts and Voltage Drop
Test a condenser contactor the right way, from 24 V at the coil and coil resistance to pitted contacts and voltage drop under load.
How to Test a Run Capacitor: Meter Method and Under-Load Method
Test HVAC run capacitors two ways, with the meter's capacitance setting and under load with amps × 2652 ÷ volts, and know when to replace one.
Field reference for trained technicians. Always follow the equipment manufacturer's instructions, local code and safe work practices. See our editorial standards, or report a correction.