AC Outdoor Unit Humming but Not Running: Capacitor, Contactor, Fan Motor or Compressor?
A humming outdoor unit has power. The contactor has closed and voltage is getting to the compressor, the fan motor or both, but something isn't turning. That narrows the problem a lot. If it's only the compressor that won't start, AC compressor not starting goes deeper on that branch.
Safety: Don't let it sit there humming. A compressor that can't start draws locked-rotor amps and heats up fast until its internal overload opens. Kill power at the disconnect, then discharge the capacitor before you touch anything.
What's humming?
| What you see and hear | Most likely | Check |
|---|---|---|
| Fan not turning, compressor not running, loud hum | Weak or failed capacitor (often the common side of a dual), or a seized fan motor | Capacitor, then spin the fan |
| Fan running, compressor humming but not starting | HERM side of the capacitor, a hard-starting or locked compressor, or low voltage | Capacitor, supply voltage, then compressor |
| Fan humming but not turning, compressor running | FAN side of the capacitor or a seized fan motor | Capacitor, then the fan bearings |
| Buzz or chatter at the contactor, nothing starts | Low 24 V to the coil, or pitted contacts | Coil voltage and contact voltage drop |
| Hums, then trips the breaker | Locked or grounded compressor, a shorted wire | Stop and ohm the compressor |
Check in this order
- Capacitor. It's the most common cause and the cheapest fix. With power off and the capacitor discharged, measure each side with a meter. See how to test a run capacitor. The part finder tells you whether your reading is in tolerance and lists replacements.
- Fan motor. With power off, spin the blade by hand. It should turn freely and coast. If it's stiff or won't turn, the bearings are gone: see condenser fan not spinning and how to replace a condenser fan motor.
- Contactor. Check the coil gets 24 V on a call, then measure the voltage drop across each closed contact under load. Burned or pitted contacts can pass enough voltage to hum but not enough current to start. See how to test a contactor.
- Supply voltage. Measure line voltage at the contactor while the unit tries to start. A big sag points at the supply, a loose connection or a failing breaker.
- Compressor. If the capacitor and contactor are good and the compressor still hums without starting, ohm the windings and check for a ground. See how to test a compressor. Good windings but no start usually means a mechanically tight compressor; a hard start kit may get it running.
Common mistakes
- Leaving it humming while you diagnose. Every attempt to start a locked compressor heats the windings.
- Swapping the compressor before testing the capacitor. A failed capacitor makes a good compressor hum and trip.
- Testing only one side of a dual capacitor. Measure both HERM to C and FAN to C.
- Ignoring why the capacitor failed. High head pressure from a dirty condenser or a slow fan kills capacitors too.
FAQ
Why is my AC humming but the fan isn't spinning?
Usually a failed capacitor or a seized fan motor. With power off, spin the blade by hand: if it turns freely, test the capacitor; if it's stiff, the motor's bearings have failed.
Can a bad capacitor make the compressor hum?
Yes. Without its capacitor, a PSC compressor can't start. It hums, draws locked-rotor amps and trips its internal overload.
Is it safe to push the fan blade to get it started?
Don't. If spinning it by hand starts the fan, the capacitor or motor is bad and needs replacing. Reaching into a powered unit is how people get hurt.
The compressor hums and trips the breaker. Is it dead?
Not always. Test the capacitor and the windings first. A grounded or open winding means the compressor has failed; good windings and a good capacitor point to a locked or hard-starting compressor.
Sources
One field tip a week
A short, practical HVAC tip in your inbox every week: diagnostics, charging, airflow and code changes. Free, unsubscribe anytime.
We'll only use your email for the newsletter. Privacy policy.
Tools for this job
Related guides
Condenser Fan Not Spinning: Capacitor, Motor or Control?
Find out why an outdoor condenser fan won't run, from the fan capacitor and seized bearings to the contactor, wiring and heat pump defrost.
AC Compressor Not Starting: Humming, Clicking or Nothing at All
Diagnose a compressor that won't start by what it does: humming points to capacitor or locked rotor, clicking to overload, silence to the control circuit.
AC Breaker Keeps Tripping: How to Find Out Why
How to diagnose an air conditioner or heat pump that keeps tripping its breaker: a grounded compressor, a locked rotor, a shorted fan motor, wiring faults, high head pressure or a weak breaker.
How to Replace a Condenser Fan Motor: Matching, Rotation, Wiring and Blade Height
How to pick a replacement condenser fan motor that actually fits (HP, RPM, voltage, shaft, mounting), read CW and CCW rotation correctly, wire a single-speed PSC motor, set the blade and check amps after the swap.
Field reference for trained technicians. Always follow the equipment manufacturer's instructions, local code and safe work practices. See our editorial standards, or report a correction.