Three-Phase Voltage Imbalance Calculator

Enter the three leg-to-leg voltages at a three-phase unit, or the amp draw on each leg, and get the percent imbalance with a pass or fail against the manufacturer's limit.

V
V
V
Imbalance
–
Average
–
Furthest from average
–

How it works

% imbalance = 100 × (largest deviation from average) ÷ average

  1. Measure all three phase-to-phase voltages: L1 to L2, L2 to L3 and L1 to L3.
  2. Average them.
  3. Find the reading furthest from the average.
  4. Divide that difference by the average and multiply by 100.

Carrier's worked example for a 230-volt, three-phase supply: readings of 224, 231 and 226 V average 227 V. The furthest reading is 4 V away, so the imbalance is 100 × 4 ÷ 227 = 1.76%, which passes.

The limits

  • Voltage: 2%. Carrier's rooftop unit instructions say voltages between phases must be balanced within 2 percent.
  • Current: 10%. The same instructions say current must be balanced within 10 percent.
  • The voltage at the compressor terminals while it runs must also be inside the range on the unit nameplate.

If the supply voltage imbalance is over 2%, Carrier's instruction is to contact the electric utility. It also warns that running a unit on improper line voltage or excessive phase imbalance counts as abuse and can void the warranty. Other manufacturers may print a different limit, so check the installation instructions for the unit you're working on.

Related: rooftop unit start-up checks and economizer setup and troubleshooting.