Walk-In Cooler and Freezer Maintenance Checklist

Quarterly, semi-annual and annual PM for walk-in condensing units and unit coolers, with spaces for pressures, superheat and amps.

Condensing unit schedule follows Heatcraft's H-IM-CU preventive maintenance guidelines. The equipment manufacturer's instructions win.

Saves on this device as you type. Nothing is sent to us.
Job
Equipment
Quarterly: condensing unit
No oil stains on piping or condenser coilSolder joints, building penetrations, pipe clamps; check suspect spots with a leak detector
Moisture indicator / sight glass: dry, no flash gas
Compressor oil level OK (sight glass)
Condenser free of dirt and debris
No unusual noise or vibration
Wiring: no wear or discoloration
Flare connections checked and tightened
Semi-annual: condensing unit
Condenser coil and blades cleaned and rinsedNo acid-based foam cleaner
Each fan turns freely and quietly; set screws tight; blades not cracked
Fan motors mounted securely; lubricated if applicable
Electrical and ground connections tight
Compressor and heater contactors not pitted or discolored
Timers, relays, pressure and safety controls checked
Electrical cabinet clean and dry
Crankcase heater ampsA
Suction pressurepsig
Discharge pressurepsig
Net oil pressure (if applicable)psi
Compressor superheatPer compressor spec°F
Compressor amps (RLA / measured)A
Supply voltageV
Pressure drop across filters and driers OK
Annual: condensing unit
Oil sample sent for analysis
Suction accumulator inspected for leaks and corrosion (if equipped)
Box and unit cooler
Box temperature (set / actual)°F
Evaporator coil clear of frost and ice after defrost
Unit cooler fans running; guards and blades free of ice
Drain pan and drain line clear; drain heater working (freezers)
Evaporator superheat°F
Defrosts per day / defrost length / fail-safe# / min / min
No ice on ceiling around the unit cooler
Door gaskets and closers seal; strip curtain in place (if used)
Notes and recommendations