Servicing R-22 Systems in 2026: Recharging, Retrofits and Repair-or-Replace
Most R-22 systems still running are 15 to 30 years old. They show up on service calls every summer, and the refrigerant decisions matter more on them than on anything else you'll touch.
What the rules allow
- Production and import of new R-22 ended in the U.S. on January 1, 2020.
- Servicing existing systems is allowed. You can use recovered and reclaimed R-22, or R-22 produced before 2020.
- Venting is never allowed. Recover it like any other refrigerant; you need EPA 608 certification to buy and handle it.
- New R-22 systems can't be made. "Dry" condensers sold to be charged in the field with R-22 were also restricted years ago.
See HFC rules for technicians for the newer rules on R-410A and the systems that replace it.
Before you add R-22
- Confirm it's R-22 on the data plate and service valves.
- Check airflow and the condenser first. See superheat vs. subcooling.
- Find the leak. Topping off an R-22 system without a leak search is the most expensive thing you can do for the customer. See how to find a refrigerant leak.
- Use the R-22 PT chart: the R-22 PT chart gives saturation temperatures for superheat and subcooling.
- Give the customer the cost up front, including the leak repair, before charging.
Retrofit refrigerants
Several refrigerants are sold for converting R-22 systems. They are not drop-ins: each has its own procedure, and results vary by system.
| Refrigerant | Notes |
|---|---|
| R-407C | Close to R-22 in capacity; has significant glide; usually needs the mineral oil replaced with POE oil |
| R-422B | Designed to work with mineral oil in many systems; some capacity loss |
| R-438A (MO99) | Designed to work with mineral oil in many systems; some capacity loss |
All of these are blends with glide, so charge as liquid and use dew and bubble points. See how to read a PT chart.
Retrofit steps in general:
- Record baseline readings with R-22 if the system runs.
- Recover all R-22. Never mix refrigerants.
- Change oil if the refrigerant maker requires it; some retrofits require several oil changes.
- Replace the filter drier, and check whether the TXV or piston needs changing or adjusting.
- Evacuate to a deep vacuum. See how to pull a deep vacuum.
- Charge the new refrigerant as liquid, starting below the original R-22 weight as the refrigerant maker's guide directs, then adjust by superheat or subcooling.
- Label the system with the new refrigerant and oil so the next tech doesn't add R-22.
Repair or replace?
| Situation | Usually |
|---|---|
| Small, findable leak; system in good shape | Repair the leak, recharge with R-22 |
| Leaking evaporator coil on an old system | Replace the system, or retrofit only if the customer can't replace now |
| Failed compressor | Replace the system |
| Recurring leaks, rusty coils, poor efficiency | Replace the system |
| Customer needs to get through a season | A careful repair, with the long-term plan in writing |
Give the customer the numbers: the cost of the repair and refrigerant, the age of the system, and what a new system costs. Many shops use a rule of thumb like age × repair cost compared with the price of a new system, but the decision is the customer's.
Common mistakes
- Topping off without finding the leak.
- Mixing a retrofit refrigerant with leftover R-22.
- Calling a retrofit refrigerant a "drop-in" to the customer.
- Not labeling a retrofitted system.
- Using R-410A or R-454B PT values on R-22 or a retrofit blend.
- Skipping the oil question on retrofits that need POE.
FAQ
Can you still buy R-22?
Yes, as recovered, reclaimed or previously made refrigerant, and only by certified technicians. Supply is shrinking and prices are high.
Is it illegal to have an R-22 air conditioner?
No. Homeowners can keep using and repairing R-22 systems.
Can you put R-410A in an R-22 system?
No. R-410A runs at much higher pressures and needs different oil and components.
Sources
One field tip a week
A short, practical HVAC tip in your inbox every week: diagnostics, charging, airflow and code changes. Free, unsubscribe anytime.
We'll only use your email for the newsletter. Privacy policy.
Related guides
How to Find a Refrigerant Leak: Methods, Common Spots and the Standing Pressure Test
A step-by-step leak search for AC and heat pump systems, the leak detection methods and where each works best, the most common leak spots, and how to confirm the repair.
Superheat vs. Subcooling: What Each Tells You and When to Charge by Which
What superheat and subcooling measure, how to take them, which one to charge by for TXV and fixed-orifice systems, and how to read them together.
AC Breaker Keeps Tripping: How to Find Out Why
How to diagnose an air conditioner or heat pump that keeps tripping its breaker: a grounded compressor, a locked rotor, a shorted fan motor, wiring faults, high head pressure or a weak breaker.
AC Short Cycling: Why the Compressor Turns On and Off Too Often
How to diagnose an air conditioner or heat pump that short cycles, using how long it runs and what stops it: thermostat problems, safety switches, low charge, airflow, and oversizing.
Field reference for trained technicians. Always follow the equipment manufacturer's instructions, local code and safe work practices. See our editorial standards, or report a correction.