How to Pull a Deep Vacuum: Micron Targets and the Decay Test
Evacuation removes air (non-condensables) and moisture. Moisture in a POE oil system turns into acids and sludge, and air raises head pressure. The micron gauge and the decay test are how you prove the job is done, not the clock.
Step 1: Pressure test with nitrogen first
Find leaks under pressure, not under vacuum. Pressurize with dry nitrogen (never oxygen or compressed air) to the manufacturer's test pressure, and watch for a pressure drop, correcting for temperature changes. Fix leaks now. Hunting for leaks in a vacuum pulls moisture-laden air into the system.
Step 2: Set up the rig for speed
- Core removal tools on both service ports. Valve cores are the biggest restriction.
- Short, large-diameter vacuum hoses (3/8" or 1/2" where you can), not standard charging hoses.
- Micron gauge at the system, as far from the pump as practical, often on the side port of a core tool. A gauge at the pump reads the pump, not the system.
- Fresh pump oil. Contaminated oil can't reach a deep vacuum. Blank-off test the pump: it should pull well below 50 microns on its own.
- A2L systems: use a vacuum pump that's rated or approved by its manufacturer for A2L refrigerants.
Step 3: Evacuate
Pull down below 500 microns. Many manufacturers and trainers recommend going lower on POE oil systems. HVAC School, for example, recommends pulling below about 300 microns and confirming the system holds under about 500. Time depends on system size, moisture and rig. Don't stop at a time limit; stop at a reading.
Triple evacuation (pull down, break with nitrogen, pull down again) helps on wet systems or when you're cleaning up after a burnout.
Step 4: The decay test
Close the core tools to isolate the system from the pump and hoses. Watch the micron gauge for 10–15 minutes:
| What you see | What it means |
|---|---|
| Rises a little and holds below about 500 microns | Dry and tight, ready to charge |
| Rises, then levels off higher (about 1,000–1,500) | Moisture still boiling off. Keep evacuating |
| Keeps climbing toward atmosphere | Leak. Go back to the nitrogen test |
Some rise is normal as the pressure evens out between the system and the gauge. What matters is whether it levels off and where.
Step 5: Release the charge or weigh in
Once the decay test passes, open the service valves (new install) or weigh in the charge per the installation instructions. Break the vacuum with refrigerant, not with air.
FAQ
Is 500 microns good enough?
500 microns is the common minimum, and many manufacturers specify it. Many experienced techs pull deeper (300 or lower) and require the system to hold below 500 during the decay test, especially on POE oil systems.
Why won't my vacuum go below 1,000 microns?
Usual causes are moisture in the system, a leak, contaminated pump oil, leaking hoses or gaskets, or valve cores left in. Isolate the pump and gauge to find out which side the problem is on.
How long should a decay test be?
10–15 minutes is common for residential systems. Larger systems may need longer to stabilize.
Sources
One field tip a week
A short, practical HVAC tip in your inbox every week: diagnostics, charging, airflow and code changes. Free, unsubscribe anytime.
We'll only use your email for the newsletter. Privacy policy.
Tools for this job
Related guides
400 CFM per Ton: Where the Rule Comes From and When It's Wrong
Why 400 CFM per ton is the default cooling airflow, when to set airflow lower or higher, and how to check what a system is actually moving.
AC Compressor Not Starting: Humming, Clicking or Nothing at All
Diagnose a compressor that won't start by what it does: humming points to capacitor or locked rotor, clicking to overload, silence to the control circuit.
AC Not Cooling? A Step-by-Step Diagnostic Checklist for Techs
Work an AC no-cool call in the right order, from the thermostat call to airflow, electrical and refrigerant charge, without guessing.
Condenser Fan Not Spinning: Capacitor, Motor or Control?
Find out why an outdoor condenser fan won't run, from the fan capacitor and seized bearings to the contactor, wiring and heat pump defrost.
Field reference for trained technicians. Always follow the equipment manufacturer's instructions, local code and safe work practices. See our editorial standards, or report a correction.