Duct Size Calculator

Equal-friction sizing for galvanized sheet metal duct. Enter airflow and friction rate; pick a height for the rectangular size.

CFM
in. w.c./100 ft
Round duct
12"
Rectangular
12 × 8"
Exact round size
10.3in
Velocity (round)
509FPM
Velocity (rect.)
600FPM
Friction (round)
0.037in./100 ft

How it works

Friction per 100 ft = 0.109136 × CFM^1.9 ÷ D^5.02
Rectangular equivalent (Huebscher) = 1.30 × (a × b)^0.625 ÷ (a + b)^0.25

The calculator solves for the round diameter that carries your airflow at your friction rate, rounds up to the next standard size, then finds the narrowest rectangle (in 2-inch steps) at your chosen height with the same or better friction. Results assume standard air and smooth galvanized duct.

Notes for the field

  • Flex duct has much higher friction than sheet metal, even fully stretched. Size flex up, and pull it tight.
  • The friction rate should come from the blower's available static pressure divided by the total effective length (Manual D). 0.06–0.10 in. w.c. per 100 ft is a common residential range.
  • Keep residential supply branches under roughly 700–900 FPM to avoid noise.