Furnace Airflow from Temperature Rise

Estimate furnace airflow from the rating plate and a supply/return temperature split, and check the rise against the rated range.

BTU/h
%
°F
°F
°F
°F
Estimated airflow
–
Temperature rise
–
Heat output
–

How it works

Output = input BTU/h × AFUE
CFM = output ÷ (1.08 × temperature rise)

1.08 is the sensible heat factor for standard air (60 minutes × 0.075 lb/ft³ × 0.24 BTU/lb·°F). The answer is an estimate: it assumes the furnace is firing at its rated input. Clock the gas meter or check manifold pressure if you suspect it isn't.

Taking the temperatures

  • Let the furnace run on high fire for 10–15 minutes first.
  • Measure supply air out of sight of the heat exchanger, so radiant heat doesn't skew the probe.
  • Measure return air before the filter and any humidifier bypass.
  • The acceptable rise range is printed on the furnace rating plate.