EPA 608 Type I Study Guide (Small Appliances)
Type I covers small appliances: equipment manufactured, charged and hermetically sealed at the factory with 5 lb or less of refrigerant. Think household refrigerators and freezers, window AC units, dehumidifiers, water coolers and vending machines. You also need to pass Core.
What counts as a small appliance
- Factory sealed, 5 lb or less.
- Not small appliances: split systems charged in the field, even small ones, and motor vehicle AC (that's Section 609).
Recovery requirements (memorize these)
For recovery equipment made after November 15, 1993:
| Compressor condition | Required recovery |
|---|---|
| Compressor working | 90% of the charge, or a 4 in. Hg vacuum |
| Compressor not working | 80% of the charge, or a 4 in. Hg vacuum |
Equipment made before November 15, 1993 must recover 80% or reach 4 in. Hg vacuum.
Recovery equipment types
- Self-contained (active): has its own compressor and pushes refrigerant into a pressurized recovery cylinder. Works with a dead or working appliance compressor.
- System-dependent (passive): relies on the appliance's own compressor or pressure, and captures refrigerant in a non-pressurized container (such as a recovery bag). Only allowed for small appliances.
Tips for a dead compressor with passive recovery:
- Install access fittings on both the high and low sides.
- Heat and tap the compressor to release refrigerant trapped in the oil.
- Use a vacuum pump to help pull the remaining refrigerant into the container.
Access fittings
- Piercing (line tap) valves are common on small appliances. They tend to leak over time.
- Leak test them, and remove or replace them with proper fittings when service is done.
Know the refrigerant before you recover
- Read the nameplate. Don't mix refrigerants in a recovery cylinder; mixed refrigerant can't be reclaimed easily.
- Some very old appliances used sulfur dioxide, methyl formate or ammonia. These are toxic and corrosive and are not recovered with standard equipment. Follow safety procedures.
- A burned-out compressor leaves acid in the oil and a strong odor. Wear protective gear and clean the system before recharging.
Disposal
The person taking the last step in the disposal chain (often a scrap recycler or landfill) must make sure the refrigerant was recovered, usually by getting a signed statement that includes who recovered it and when.
Quick review
- 5 lb or less, factory sealed.
- 90% (working compressor) or 80% (not working), or 4 in. Hg vacuum, for equipment after Nov 15, 1993.
- Passive recovery: non-pressurized container, both sides accessed, heat and tap the compressor.
- Leak test piercing valves; remove them after service.
Test yourself: Type I practice questions
12 questions in this set. Passing on the real exam is 70% per section (18 of 25).