R-454B PT Chart

Quick answer

At 40°F, R-454B is about 107.7 psig at the dew point (vapor) and 113.3 psig at the bubble point (liquid). At 100°F it's about 291.6 / 303.6 psig. Look up any reading below, or print the full chart.

One of the two main A2L refrigerants replacing R-410A in new residential equipment. It has a small temperature glide, so it has separate liquid (bubble) and vapor (dew) columns.

psig
°F

Prints the full chart on one page.

R-454B (Opteon XL41, Solstice 454B, Puron Advance) · Safety class A2L · Blend: R-32 (68.9%) / R-1234yf (31.1%), zeotropic

°F°CLiquid (bubble) psigVapor (dew) psig
-38-38.911.210.0
-36-37.812.511.2
-34-36.713.812.5
-32-35.615.313.9
-30-34.416.715.3
-28-33.318.216.7
-26-32.219.818.2
-24-31.121.419.8
-22-30.023.121.4
-20-28.924.923.0
-18-27.826.724.8
-16-26.728.626.6
-14-25.630.528.4
-12-24.432.530.3
-10-23.334.632.3
-8-22.236.734.4
-6-21.139.036.5
-4-20.041.238.7
-2-18.943.640.9
0-17.846.143.3
2-16.748.645.7
4-15.651.248.1
6-14.453.850.7
8-13.356.653.3
10-12.259.556.1
12-11.162.458.9
14-10.065.461.8
16-8.968.564.7
18-7.871.767.8
20-6.775.070.9
22-5.678.474.2
24-4.481.877.5
26-3.385.480.9
28-2.289.184.4
30-1.192.988.1
320.096.891.8
341.1100.795.6
362.2104.899.5
383.3109.0103.6
404.4113.3107.7
425.6117.8112.0
446.7122.3116.3
467.8126.9120.8
488.9131.7125.4
5010.0136.6130.1
5211.1141.6134.9
5412.2146.7139.8
5613.3152.0144.9
5814.4157.4150.1
6015.6162.9155.4
6216.7168.6160.8
6417.8174.3166.4
6618.9180.2172.1
6820.0186.3178.0
7021.1192.5184.0
7222.2198.8190.1
7423.3205.3196.4
7624.4211.9202.8
7825.6218.7209.3
8026.7225.6216.1
8227.8232.7222.9
8428.9239.9229.9
8630.0247.3237.1
8831.1254.8244.4
9032.2262.5251.9
9233.3270.4259.6
9434.4278.4267.4
9635.6286.6275.4
9836.7295.0283.6
10037.8303.6291.6
10540.6325.7313.6
11043.3348.9336.4
11546.1373.4360.5
12048.9399.1385.8
12551.7426.0412.4
13054.4454.2440.5
13557.2483.8470.0
14060.0514.9501.0
14562.8547.3533.7
15065.6581.4568.2

How to use a PT chart

A PT chart gives the temperature at which a refrigerant boils or condenses at a given pressure. Read your gauge, find the saturation temperature, then compare it with the line temperature you measure:

  • Superheat = suction line temperature − saturation temperature at suction pressure (use the dew column).
  • Subcooling = saturation temperature at liquid pressure − liquid line temperature (use the bubble column).

The superheat and subcooling calculator does the math, and how to read a PT chart walks through it step by step. Always charge to the equipment manufacturer's instructions.

Source

Values are from the Daikin Comfort Technologies A1 vs. A2L pressure-temperature chart (data provided by Weitron), and were spot-checked against other manufacturer charts. Interpolated lookups are estimates.

Field reference only. Confirm against the refrigerant manufacturer's data and the equipment manufacturer's charging instructions. Spot an error? Tell us.