Home / Charts / R-410A

R-410A PT Chart

Quick answer

At 40°F, R-410A is about 118.6 psig. At 100°F it's about 318.1 psig. Look up any reading below, or print the full chart.

The standard residential AC and heat pump refrigerant from about 2010 until the 2025 switch to A2L refrigerants. Still in millions of systems and still serviced.

psig
°F

Prints the full chart on one page.

R-410A (Puron) · Safety class A1 · Blend: R-32 (50%) / R-125 (50%), near-azeotropic

°F°Cpsig
-38-38.912.1
-36-37.813.4
-34-36.714.8
-32-35.616.2
-30-34.417.8
-28-33.319.4
-26-32.220.9
-24-31.122.6
-22-30.024.4
-20-28.926.2
-18-27.828.1
-16-26.730.1
-14-25.632.1
-12-24.434.2
-10-23.336.4
-8-22.238.6
-6-21.140.9
-4-20.043.3
-2-18.945.8
0-17.848.3
2-16.751.0
4-15.653.6
6-14.456.5
8-13.359.4
10-12.262.3
12-11.165.3
14-10.068.5
16-8.971.8
18-7.875.1
20-6.778.6
22-5.682.1
24-4.485.7
26-3.389.4
28-2.293.2
30-1.197.2
320.0101.2
341.1105.4
362.2109.7
383.3114.1
404.4118.6
425.6123.2
446.7127.9
467.8132.8
488.9137.8
5010.0142.9
5211.1148.2
5412.2153.5
5613.3159.0
5814.4164.7
6015.6170.4
6216.7176.3
6417.8182.4
6618.9188.6
6820.0194.9
7021.1201.4
7222.2208.1
7423.3214.8
7624.4221.8
7825.6228.9
8026.7236.2
8227.8243.6
8428.9251.1
8630.0258.9
8831.1266.9
9032.2274.9
9233.3283.1
9434.4291.6
9635.6300.2
9836.7309.1
10037.8318.1
10540.6341.4
11043.3365.9
11546.1391.8
12048.9418.9
12551.7447.4
13054.4477.4
13557.2508.9
14060.0542.0
14562.8576.8
15065.6613.5

How to use a PT chart

A PT chart gives the temperature at which a refrigerant boils or condenses at a given pressure. Read your gauge, find the saturation temperature, then compare it with the line temperature you measure:

  • Superheat = suction line temperature − saturation temperature at suction pressure.
  • Subcooling = saturation temperature at liquid pressure − liquid line temperature.

The superheat and subcooling calculator does the math, and how to read a PT chart walks through it step by step. Always charge to the equipment manufacturer's instructions.

Source

Values are from the Daikin Comfort Technologies A1 vs. A2L pressure-temperature chart (data provided by Weitron), and were spot-checked against other manufacturer charts. Interpolated lookups are estimates.

Field reference only. Confirm against the refrigerant manufacturer's data and the equipment manufacturer's charging instructions. Spot an error? Tell us.