400 CFM per Ton: Where the Rule Comes From and When It's Wrong
"400 CFM per ton" is the first airflow number every tech learns. It's a good default, but treat it as a starting point and check it against the manufacturer's spec and the actual airflow.
Where 400 comes from
A ton is 12,000 BTU/h. At about 400 CFM per ton, a typical evaporator coil runs cold enough to remove a reasonable amount of moisture while still delivering most of its capacity as sensible cooling. It's a middle-of-the-road balance between temperature and humidity control.
When to go lower or higher
| Climate / goal | Typical airflow | Why |
|---|---|---|
| Humid (Gulf Coast, Southeast) | about 350 CFM/ton | A colder coil removes more moisture |
| Average | about 400 CFM/ton | Balanced |
| Dry (desert Southwest) | about 450 CFM/ton | Little moisture to remove, so more sensible capacity |
Many variable-speed blowers and communicating systems have dehumidify or humid/dry climate settings that do this automatically. Too little airflow in any climate risks a frozen coil and floodback. Too much airflow cuts moisture removal and can blow condensate off the coil.
Always check the manufacturer's specs. Some equipment, especially inverter heat pumps, publishes its own airflow targets per mode and stage.
Measure, don't assume
Duct systems often restrict airflow well below the setting. Ways to measure actual airflow:
- Fan table + total external static pressure: read TESP, then look up CFM at that static and speed tap in the equipment's blower table. See total external static pressure.
- Temperature rise method (heating): on a gas furnace, CFM = output BTU/h ÷ (1.08 × temperature rise). Use the furnace airflow calculator.
- Flow grid or flow hood: direct measurement at the filter slot or at the registers.
Heat pumps and heating airflow
Heat pumps often run similar airflow in heating and cooling. Gas furnaces set heating airflow by temperature rise, not by tons. Check the rise against the rating plate range.
FAQ
How many CFM does a 3-ton system need?
At 400 CFM per ton, 1,200 CFM nominal. Somewhere between 1,050 (350/ton) and 1,350 (450/ton) depending on climate and the manufacturer's spec.
Does lower airflow improve dehumidification?
Yes, up to a point. A slower airflow makes a colder coil, so it removes more moisture, but too low risks freezing the coil.
How do I change blower airflow?
On PSC blowers, change the speed tap. On ECM and variable-speed blowers, change DIP switch, tap or control board settings per the installation manual.
Sources
One field tip a week
A short, practical HVAC tip in your inbox every week: diagnostics, charging, airflow and code changes. Free, unsubscribe anytime.
We'll only use your email for the newsletter. Privacy policy.
Tools for this job
Furnace Airflow from Temperature Rise
Estimate furnace CFM from input BTU, efficiency and the supply/return temperature rise.
DUCTDuct Size Calculator
CFM and friction rate in; round and rectangular duct size, velocity and friction out.
UNITSHVAC Unit Converter
Tons, BTU/h and kW; °F and °C; psi, kPa and in. w.c.; CFM and L/s; oz, lb and kg.
Related guides
Total External Static Pressure: How to Measure It and What's Normal
Measure total external static pressure with a manometer, compare it to the equipment's rating, and use it to find airflow restrictions.
AC Compressor Not Starting: Humming, Clicking or Nothing at All
Diagnose a compressor that won't start by what it does: humming points to capacitor or locked rotor, clicking to overload, silence to the control circuit.
AC Not Cooling? A Step-by-Step Diagnostic Checklist for Techs
Work an AC no-cool call in the right order, from the thermostat call to airflow, electrical and refrigerant charge, without guessing.
Condenser Fan Not Spinning: Capacitor, Motor or Control?
Find out why an outdoor condenser fan won't run, from the fan capacitor and seized bearings to the contactor, wiring and heat pump defrost.
Field reference for trained technicians. Always follow the equipment manufacturer's instructions, local code and safe work practices. See our editorial standards, or report a correction.